b). Tt�e addidon of the decks create floor area, per definition Secdon 207. Based on <br /> the distance to propecty line requirements, this tloor area is required to be protected <br /> by twahour, firo-resistive exterior wall constcucdon. In essence, what is currendy <br /> shown is equivalent to unprotected openings within the ezterior wall. Table.5-A <br /> c). Similazly, tha decks and storage units on the west elevadon represent floor area <br /> that is required to be protected by ezterior walis and opening protecdon. <br /> 6. Projecdons beyond the ezterior wall shall comply with Section 705 and shall not <br /> eztend beyond a point one third the distance to the property line from an assumed <br /> vertical plane located where fice-resisdve protection of openings is first required due <br /> to location on property. Specifically,the projections beyond the exterior walls may be <br /> located no closer than 13'-4" to the respective property lines (provided the <br /> requirements in comment#Sb are satisfied). <br /> 7. Combustible projections located where openings are not permitted or where <br /> protection of openings is required shall be of one-hour fire-resistive or heavy-timber <br /> conswction confomung to Section 605.6. Details of the projections should be <br /> provided on the plans. Section 705 <br /> 8. The sum of the area of openings in exterior walls required to be protected due to <br /> distance from property lines should not ezceed 50 petcent of the total area of the wall <br /> in each story. Due to the lazge amount of glazing shown, the East and West walls <br /> should have a typical floor level (2,3 or 4) analyzed and submitted to show <br /> compliance. Section 503.2.2 <br /> 9. Pazapet walls are required on every ezterior wall less than 20' from the prope�ty line <br /> unless the walls will terminate at roofs of not less than two-hour fire-resisdve <br /> conswcdon, or roofs constructed enticely of noncombustible materials (note thut fire- <br /> retardant-treated lumber is not permitted). The effected walls should be shown on the <br /> plans as well as the construction of the pazapet in accordance with Secdon?09.4. <br /> 10. In fire-resistive exterior wall conswction, the fia-cesisdve radng shall be maintained <br /> for such walls passing through attic areas or other arcas containing concealed spaces <br /> per Section 709.3.1 The floor/ceiling assemblies should be shown a, having the twa <br /> hour fire-resistive conswcdon continue through that void space at the intereonnection <br /> between the walls and floors. Note that the TJI's shown within the floor cavity in <br /> Details 10 & 11/S-16 are not sufficient to maintain the fire-resistive constiuction <br /> requirements of the wall assembly. <br /> 11.The North and 5outh exterior walls are set back from the propecty lines incrementally. <br /> The following comments apply to those walls: <br /> 3 <br />