4. The accessible parking spaces on Floor 1 should be located on the shoctest possiblc <br /> accessible route of vavelto the accessible lobby entrance. Section 1107.1.6 <br /> 5. The access aisle adjacent to the accessible pazking spaces on Floor 1 should shown as <br /> a minimum of 60 inches in width. Section 1107.2.2 <br /> 6. Boundazies of the access aisles on Floor PI should be marked so t6atthe aisles will <br /> not be used as parking space. Secdon 1107.2.2 <br /> 7. Curbs, guardrails, or raised "bump"-rype detectable warning surfaces should be <br /> provided where the accessible route of travel crosses or adjoins vehicular areas. <br /> Sections 1106.4.8 and 1106.17 <br /> 8. The maximum slope of the curb cut ramps should be shown. Secdons 1106.4.7.1 � <br /> I 106.4.73 <br /> Interior Accessibility <br /> 1. Meac of evacuation assistance and all their details such as size, locadon, telephone, <br /> ,-ue protecdon, signs, etc. should be shown. Focty-eight inches clear width between <br /> handrails in each stairway is also required for evacuation. Section 1104 <br /> 2. In lieu of tt�e above requirement, A written emergency plan which addresses the <br /> evacuation of persons with disabilides should be submitted for review by the building <br /> official and fire mazshal. The approved plan will be kept on pecmanent file with the <br /> plans and should also be maintained on-site. A note regazding the modified sprinkler <br /> system should be shown with the Firo Sprinkler Protxtion notes on the cover sheet. <br /> Sution 1104 <br /> 3. Door thresholds should be shown as no higher than 1/2". The edges should be <br /> beveled at 1 vertical : 2 horizontal, with a maximum edge height of 1/4". Sections <br /> 1106.10.4& 1106.6 <br /> 4. Forward approach to a door which must be pulled open requiros a minimum clearance <br /> of 60 inches perpendiculaz to the door and a minimum side clearance of 18 inches <br /> next to the latch on the approach side. The doors between the corridors and ezterior <br /> exit balconies(uound the interior court)should either be removed or revised. Section <br /> I 106.103 itent 1 <br /> 5. For the toilet room within the recreatior, space and Type A dwelling units: <br /> a). The water closet seat height should be at t7"-19" from the floor. Sxtion <br /> l 106.11.5.2 <br /> 16 <br />