Laserfiche WebLink
(� (. <br /> ENGINEERING / PUBL/C SERI/lCES DEPARTMENT <br /> , oo� <br /> 4. IBC 704.5 requires exterior walls that are five feet of less from property lines to be of <br /> one-hour fire-resistive constnrction that is rated for exposure from both sides. Should <br /> the five feet dimension remain, a cross section of the wall will be required that includes <br /> all wnstruction details and the testing agency identification number. <br /> 5. IBC 704.2.3 requires the eave overhangs on the right and left sides to be at least one- <br /> hour fire-resistive construction, fire-retardant-treated wood, or protected by exterior <br /> sprinkler heads. <br /> 6. The door separating the garage from the stairway is required to be solid wood or <br /> honeycomb core steel not less than 1 3/8" inches and be self-closing and sel;-latching. <br /> IBC 406.1.4. <br /> 7. IBC 1013.2 requires the guards to be a minimum of 42" high. <br /> 8. IBC 2305.3.11 rec�uires the washers used with anchor bolts for shear walls to be 3 inch <br /> by 3 inch by .229 mch minimum. <br /> 9. Fire blocking should be indicated at the party wall floor and roof intersections in <br /> accordance with IBC 717. <br /> (0. F�-li3 <br /> Please prepare a response lettcr showing where each item in this correction letter is addressed <br /> on the plan set. <br /> Upon resubmittal of the drawings, your application will be given priority and plan review will <br /> recommence. <br /> All required submittals shall be of sufficient detail and contain sufficient information to ensure <br /> that the proposed structure will be constructed in compliance with all adopted codes. <br /> Sincerely, !� I M ��_ <br /> . �� �r <br /> Steve Miller <br /> Associatc Gngineer <br /> ���l� 1 <br /> CITY OF EVERETT• 3200 Cedar Street• Everett,WA 98201 •(425) 257-8800•Fax(425)257-8856 � ' ,' <br /> D[OIPINCKMST0.VAILLER�D0109-011(])06 WlI�qRC AVF�A,B l C <br />