_ t � <br />3. A shower spray unit, with a hose at least 60 inches long, that can be used as a fixed <br />shower head or as a hand-held shower, shall be provided for the Type A unit. Section <br />1106.11.9.4 <br />Energy <br />1. It should be noted on the plans that all glazing shall be certified and labeled with its <br />U-factor by an independent agency licensed by the NFRC. Section 502.1.5.1 <br />2. It should be clarified how the additional R 8 insulation is to be achieved on the 2x4 <br />construction per the note on Sheet 15. Details should be provided where this occurs <br />along with keying this requirement to the plans or elevations. <br />3. Vapor retaders having a perm ratio of one or less should be shown installed on the <br />warm side at all walls and floors separating conditioned space from unconditioned <br />space. Note that face stapl:,:g is required for walls. Section 502.1.6 <br />STRUCTURAL <br />General <br />Framing <br />Lateral <br />