Laserfiche WebLink
• a <br />Water-resistant gypsum sheathing should be specified for the stair landings where <br />one -hour fire -protection is required. A weather resistive barrier should be installed <br />over this GWB per Sections 1402.1 and 2511.1. <br />9. A class C roof should be specified on the plans. Table 15-A <br />Exiting <br />The stair rise (4 inches min, 7 1/2 inches max) and run (10 inch minimum) should be <br />shown on Detail 1/11. Section 1006.3 <br />All stair enclosure doors shall be specified to have a temperature rise not exceeding <br />450 degrees. Section 1009.3 <br />3. The ceiling of the stair enclosures is required to be a complete one -hour fire -resistive <br />assembly, otherwise the walls of the enclosures should continue to the underside of <br />the roof sheathing. Section 711.2 <br />4. The attic access hatch within the stair enclosures are not permitted and should be <br />relocated to another area. Section 1009.3 <br />5. All openings in the exterior wall of the building which are within 10 feet of <br />unprotected openings in the interior stairways should be protected with fire <br />assemblies having a 45-minute rating. These assemblies should be fixed, self -closing, <br />or automatic closing. Note that the garage door would also have to comply with this <br />requirement. Openings in the top floor are exempted. Section 1006.11 <br />6. The siding shown within the stair enclosures should be specified to have a Class I <br />Flame Spread Classification per Table 8-A and Section 804.1. <br />Accessibility <br />Details of the grab bars at the Type A unit bathtub should be provided. A grab bar is <br />required on the end wall over the drain, and 2 bars are required at the back wall. <br />Section 1106.11.9.3 <br />2. 'Be in -tub seat requirement per Section 1106.11.9.2 should be shown on the plans for <br />the Type A unit. <br />