Laserfiche WebLink
ri <br />7. Fans that penetrate the ceiling of fire -resistive assemblies require fire dampers. <br />UBC 7.13.11. <br />8. An attic access panel should be located on the plan. This must be constructed of <br />one -hour fire -resistive construction. UBC 1505.1. <br />9. Section A, Slit. 14 shows no below -grade wall insulation. WSEC 502.1.4.10. <br />Please prepare a response letter showing where each item in this correction letter is addressed on <br />the plan set. <br />Upon resubmittal of the drawings, your application will be given priority and plan review will <br />recommence. <br />All required submittals shall be of sufficient detail and contain sufficient information to ensure that <br />the proposed structure will be constructed in compliance with all adopted codes. <br />Sincerely, �/�,� • �� <br />Steve Miller <br />Associate Engineer <br />SM DEDITLY[ALMAVE IME ANT RO 2415 \�/ <br />