Laserfiche WebLink
P!!BL/C iV0?Kri � <br />Plan Check �48193 <br />May 3, 1995 <br />: age 2 <br />5. The area wells are not detailed. They should provide at least the same area as is <br />required for escape and rescue windows. The max. height from the bottom of <br />the area well shall not excced 44" to the finished grade. <br />6. When ffie valuation of a repair aiteration or addition to a single family residence <br />ezceeds 51,000 (as determined by the Building Division) smoke detectors are <br />required to be installed in all sleeping rooms and in the corridor or area giving <br />access to each separate sleeping area. Detectors shall be installed on each floor <br />and in easements. <br />7. Wazm air furnaces may not be i:istalled in a room used or designed to be used <br />as a bedroom, bathroom, closet or any enclosed space with access only through <br />such room or space. Sec. 704 UMC. <br />Upon resubmittal of the drawings, your applicaGon will be given priority and plan <br />review will recommence. <br />Sincerely, <br />/%�l r/��� <br />Jeff Heilman <br />Associate Engineer/Building <br />1H:jd:pc�l193 <br />CITY OF EVERETT• 3200 Cedar Street • Everett, WA 98201 •(206) 259-8800 • Fax (206) 259-8856 <br />