Laserfiche WebLink
, ' <br /> C C�j <br /> Jeff McFall <br /> Merch 1,2000 <br /> Page 5 of 5 <br /> 5. The flushing mechanism for ihe accr.ssible toileu should be shown located at the wide-side of <br /> the compertment Section 1106.11.5.4 <br /> 6. Only the first urinal in each toilet room should be accessible. Secrion 1106.11.6 <br /> 7. On any floor where weter fountains are provided,at least 50%should be accessible,and at least <br /> une shouid be mounted at standard height. Section I 105.4.1 <br /> 8. Drinking fountains located within alcoves greater than R" in depth shoulrl be a minimurt► of 48 <br /> inches in width. A minimum of 24 inches of clear spac.e s.houl� ►x �!r.rvided from the spout to <br /> the nearcst side wall. Section 1106.13.5 <br /> ?. The customer service windows should be shown with a minimrrm 36" long accessible portion <br /> :�o higher than 36"above the floor. Secti�n 1105.4.7.2 <br /> Prepe�e a response letter showing where each item in this cortection letter is sddressed on the plan set. <br /> Upon resubmittal of the drawings, your application will be given priority and plan rcview <br /> recommence. <br /> All rcquired submittals shall tx,of su�cient detail and contain sufficient information to ensure thst the <br /> proposed str�cture will bc constructed in compliance with all adopted codes. <br /> Sincerely, <br /> �-���'�- <br /> Ton� <br /> Associate nngineer <br /> 1CL:PL.\NCNFCK NB0001-012 <br /> 1 <br />