Laserfiche WebLink
Pat & Sandy Berger <br />Plan Check No. C0104-028 <br />May 1 l, 2001 <br />Page 2 of 2 <br />9. Provide engineering report for the use of solid sawn rim joist with L?I joists. <br />l0. Maintain minimum 1" clear air space over insulation in rafters; show on plans. <br />11. Show footings a minimum of 18" below finished grade and stem walls extending a minimum of <br />6" above the finished grade. Provide minimum 6" wood to earth clearance; show on plans. <br />12. Provide egress window in master bedroom. Window shall have minimum 5.7 square feet of <br />openablc area with minimum 24" height, minimum 20" width. 'fhe top of the sill shall not be <br />more than 44"above the finished floor. <br />13. Provide minimum %:" diameter x]0" anchor bolts at 48" o.c. 7" minimum embedment, <br />minimum 2 each piece and within 12" of each end of each piece, with 2" x 2" x 3/16" plate <br />washer on all ancf�or bolts. <br />14. Specify "grade" of LPI floor joists. <br />15. Provide smoke detectors in all sleeping rooms and in the corridor or area gi��ing access to each <br />separate sleeping area (show on plans). <br />16. Verify that double 2x4 is adequate to sup��ort giu-lam ridge beam. <br />Prepare a response letter showing where each item in this correction letter is addressed on the rlan set. <br />Upon resubmittal of the dr�:wings, your application will be given prioriry and plan review will <br />recommence. <br />All required submittals shail be of sufficier.t detail and contain sufficient information to ensure that the <br />proposed structure will be constructed in compliance with a11 adopted codes. <br />Sincerely, <br />%�L�' '�.G�L_ <br />i� <br />Jeff Heilman <br />Development Technician <br />S:VLindsay\WORDIHEILMAN, nPlen Check MC0104-028 Joc <br />