Laserfiche WebLink
. .-- � e� <br />'1. Provide min. 36" landing not more than 8" below the finished floor. <br />8. Provide detail of candlever show all componems, includiog insulation and vemilarion. <br />9. Spccify roof framing over bay windows, show WSEC requirements and ventilation. <br />10. The typical wall secdon on sheet 6 shows the 1" air space wder the insuladon bafile. <br />The air space is reyuired to be over the batile. <br />11. The rypical wall section shows scissor avsses, show on plans which portion of ausses <br />are scissors. <br />12. Provide calculations for attic ventiladon. Show siu and location of vents prr section <br />1505.3 UBC. <br />13.1'he over all dimension shown on the floor plan is not correct. <br />14. The Dimension on the window in the second bedroom (front of house, 4'-6"0 would not <br />provide min. 2'-8" wall as required for lateral bracing. <br />15. Provide 3etail of porch construction, show all components. Show size and embedment <br />of footings, post/footing connection, post/beam wnnecdon, deck joist to house <br />connection, post beam connecdon (� roof and show how roof trusses are conc�ected to <br />house. <br />Provide a response letter showing where each item in tk�.is correctiun letter is addressed on <br />the plan set. <br />Upon resubmital of the drawings, your application will be given prioriry and plan review <br />will commence. <br />All required submittals shall be of sufficient detail and contain sufficient information to <br />ensure that the proposed structuce will be consuvcted in compliance with all adopted codes. <br />Sincerely, <br />������ <br />Jeff Hei(man <br />Development Technician <br />ni:�c��io�on <br />2�Z <br />