PORT OF EVERETT CHILL FACU rrY <br />TENANT IMPROVEMENTS <br />REVISED OCTOBER 16 1992 <br />The Port of Everett (Owner) will furnish the following materials for this contract: <br />A. 1,600 If. of 3-5/8" X 25 gauge metal track. <br />B. 50 If. of 3-5/8" X 20 gauge metal track. <br />C. 270 If. of 3-5/8" X 25 gauge metal studs. <br />D. Special electrical panels as follows: NOTE REVISION OF ITEM #2 & #6 <br />1. 2 each Square D 3073H Xfmrs 480:208 W120 30 <br />2. 2 each Square D add to existing C/B's for panel PP3, FA 34040, I -line <br />C/B's. <br />3. 1 each panel RP4, 42ckt., 10013 MCB 208v/120 304w, flush IOK, 1-40/1 Ctop, 20-20/1/, . <br />4. 1 each panel RPS, 42ckt., 100/3 MCB 208v/I20 304w, flush top, 22-20/1 <br />C/B 10K, 1-4011 C/B IOK, 1-50/2 GB IOK, NP/GB. <br />5. 2 each 6013 480v FSSW H.D., N-l. <br />6. 6 each 40 amp 600v RK-S fuses. <br />