Laserfiche WebLink
Plan Chcck #C0310-0�3 <br />November 5. 2003 <br />Poon � �f 7 <br />' __.. _ ..' _ <br />7. SpeciFy connection oF new foundation to the existing foundation. <br />8. WSL'C reauires windows to be L�-0.40 or less, door� U-0.�'0 and skylignts to be U-0.58. <br />9. Specify all window sizes and location of safety glass. <br />10. Skyli�ht wells :�re required to be insulated to minimum R-21. Show on plans. <br />1 l. Skyliaht construction details should be submitted for review. <br />12. Show metal ties called out in structural notes on seclion(s). <br />l3. Drawings prepared t�y an architect arc reyuired to be wei stamped and counter signed. <br />14. Verify minimum 50 cfm fan in existin� bathroom. <br />l5. Verify minimum light and ventilation requirements are met ir. exl anded bedroom. <br />Prepare a response Ictter showing where cach item in this correction letter is addressed on the plan set. <br />Upon resubmittal of [he drawings, your application will be given priority and plan review will <br />recommence. <br />Ali required submittals shall be of sufficien[ detail and contain sufficient information to ensure that the <br />proposed structure will be consWcted in compliance with all adopted codes. <br />Sinccrcly, ' <br />, ��:' �� <br />Jeff Hci man <br />Development 7'echnician <br />S�ULinJsa�\\VOIiD\IiGll.\I:\N. 1\Plan Check #C(131U�6?3.diw <br />