Laserfiche WebLink
s; <br />; <br />:E <br />� <br />PL/BL/C /�!/O/'�X5 <br />PC #48674 <br />June 28, 1995 <br />Page 2 <br />.� <br />10. <br />11 <br />12 <br />13. <br />R-5 insulated foam sheathing on all exterior wa�ls is required per the Energy <br />Code compliance path you have chosen. Show insulated foam on section views. <br />Show on plans: Chimney to be min. 2'-0" above any structure within 10'-0". <br />Provide siair detail showing the following informati+�n: <br />a. Headroom over stairs <br />b. Fireblocldng <br />c. Handrail placement (distance) above tread nosing. <br />d. Return handrails to wall <br />Provide detail of interior guardrail at stairs, per sectio�� 1712 UBC. <br />Incorporate rafter/floor floor joist detail into plan set. <br />In order for the processing of your application to continue, it will be necessary to <br />provide the Building Division with two complete new sets of drawings reflecting ti�e <br />correcdons requested. <br />Upon resubmittal of the drawings, your application will be given priority and p'.an <br />review will recommence. <br />All required submittals shall be sufficient detail and contain sufficient informadon W <br />ensure that the proposed str�cture will be constructed in compliance with a11 adopted <br />codes. <br />Sincerely, <br />9��-�-- <br />Jeff Iieilman <br />Development Technician <br />CITY OF EVERETT• 3200 Cedar Street • Everett. WA 98201 •(206) 259-8800 • Fax (206) 259-8856 <br />