, , . <br /> a. Please remove all drawing refe�ences to ;40A' within the building, and replace with the <br /> term zaessible; per IBC section 1102.1. <br /> 2. The dining seating that is identified as accessible should have a section indicating furniture <br /> heights, per ICC A117-1-2003 section 902.1. <br /> 3. The new toilet rooms require dimensions on the side of the toilet to show the location of <br /> fixtures and equipment per ICC A117-1-2003 section 603. <br /> 4. The 60 inch turning circle cannot be reduced to 48 inches as sho�vn on the drewings without <br /> submitting specific manufacturers catalog cuts for the actual toilet fixture and sink to be <br /> installed, so that the knee and toe dearance can be verified. Otherwise, the only option to <br /> reduce required turnaround clearance is per ICC A117-1-2003 section 603.Z. <br /> 5. A section through the cashier counter should indicate the required height for accessibility, per <br /> ICC A117-1-2003 section 9043. <br /> Additional Comments <br /> 1. Plecha�ir_al, plumbing and electrical permits can be applied for and obtained after the building <br /> permii is issued. <br /> 2. New fire alarm plans should be submitted after the building permit is issued, since the layout of <br /> the building and tenant area will change with this permit, and alter the current coding of the <br /> alarm system from when it was initially installed. <br /> These comments address building issues only. Revisions or aciditions may be required by other <br /> departments (Utilities, Public Nlorks, or Planning). <br /> Upon resubmission of the drawings, plan review will resume and your application will be given priority. <br /> All required submittals must be of sufficient detail and information to ensure that the proposed <br /> structure will be constructed in compliance with all adopted codes. Code references cited include the <br /> 2009 International Building Code (IBC), the 2006 Washington State Energy Code (WSEC), and the <br /> Z003 Accessible and Usable Buildings and Facilities A1i7.1-2003 (ICC/ANSI). All codes refErenced, as <br /> amended by the City of Everett, should include current adopted and revised mdes (RCW) of the State <br /> of UJashington. Please contact me with any questions at 425-257-8813. <br /> S� cerely, <br /> Meg ale NCARB <br /> Plan Exa �ner <br /> cc: AF ]im Venturo, Fire Department <br /> Attachmenks <br /> i <br /> 3�3 i <br />