0 <br />$. Thc plans should specify mcthods of compli�ncc with tlie 1997 Washington Stalc <br />Vcntilation nnd lndoor Air Quality Code, i.c. kitchen, bath and wholc housc fans <br />ventcd to thc outside, outdoor air inlets. <br />6. The plans must specify a method of compliance with thc 1997 Washington Statc <br />Energ�� Coda Should the compliance option choscn include slab on grade <br />insulation, ilie plans must show it. The typical wall section calls for R38 Batt <br />insulation ���ithin a 2 x]0 rafter system. A deeper system would be required for <br />R38 Batt and the 1" of required air snace (sec endosed information and UBC <br />1 �05.3). <br />7. Smoke delectors are rcquired per UE3C 310.9. <br />Please prepare a response letter showing where each item in this Ictter is addressed on thc <br />plan set. <br />Upon submittal of the drawings, your application will bc gi �en prioriry and plan review <br />w•ill recommence. <br />All required submittals shall be of sufficient detail and contain sufficient information to <br />ensure that the proposed structure will b� constructed in compliance ���ith all adopted <br />codes. <br />Sinccrely, �, <br />�� <br />.✓" <br />Steve Miller <br />Associatc Engincer <br />Shtjit9911-018 <br />ZIL <br />