Laserfiche WebLink
� A <br />C <br />^-� Two exits are required as the occupant load is 31. The exits ahould be aeparatcd a <br />minimum of �h the diagonal of the building. The current separation is approzimately <br />10' ahorter than required. Section 1004.2.3.2 <br />S. A minimum 6 foot wide by 44 inches dap landing ahould be ahown at the frcnch <br />doors. The lending shoul,+ be no lower than 1" below the threshold of the doorway. <br />Sections 1003.3.1.6 & 103.3.1.7 , <br />Corotrucdon <br />1. The attic ventilation (other than soflit vents) should be specified and locat� on the <br />plans. Calculations should be provided showing a 25% reduc2ion in area due to dx <br />!i" metal mesh scrceting. Section 1503.3 <br />�2. Safety giezing should be shown for the window adjacent to the main entry door. <br />Section 2406.4 <br />3. The sleepers should be shown es treated lumber, or underfloor ventilation should be <br />provided. Section 2306.7 <br />4. The 4x4 footing posts in the crawl space should be shown as pressure treated. <br />Section 2306.5 <br />Acceseibility <br />1. A minimum of two public entrances should be accessible. Section 1103.2.3 <br />2. M accessible route of travel should be shown from the accessible entrances to the <br />public way. Section 1103.2.2. <br />3. The access aisle l.tween the accessible parking spaces should be a��inimum of 8 <br />rcet wide. Section 1107.2.2. <br />4. Each accessible parking space should be shown as having a sign 3 S feet high <br />centered at the heac! of the spece and bearing the words, "State Disabled Parking <br />Pertnit Required." Section 1107.3. <br />S. Both resvooms should be accessible. Section I 105.2.2 &.15�^.�.3.1 <br />6. Two weter fountains should be provided - one accessible and the other mounted at <br />standard height. Sections 1105.4.1 & 2903.4.1 <br />7 <br />