Laserfiche WebLink
i <br /> Dr. M. Blackburn <br /> September 28, 2005 <br /> Page 2 <br /> 10. Specify whole house ventilation system and controls. <br /> 11. Show attic ventilation calculations. Show vent type and location on plans. <br /> 12. Specify roof pitch at shed dormer. Specify on plans underlayment application for <br /> roofs from 2:12 up to 70 roofs 4:12 pitch per R905.2.7 IRC. <br /> 13. The floor plan and the "upper floor section" show floor joists running over the top of <br /> the beam please clarify. <br /> 14. Typical wall section calls out 2 x _ studs at " o•c <br /> 15. Provide 3"x3"xl/4" plate washers on all anchor bolts in braced wall lines. <br /> 16. Specify diameter of anchor bolts in typical wall section. <br /> 17. Show insulation requirements for 2 x 12 rafters. <br /> 18. Specify connection of 2 x 12 rafters to top plates at exterior walls capable of resisting <br /> uplift and lateral displacement. <br /> 19. Provide a response letter showing where each item in this correction letter is <br /> addressed on the plan set. <br /> Please prepare a response letter showing where each item in this correction letter is addressed <br /> on the plan set. <br /> Upon resubmittal of the drawings, your application will be given priority and plan review will <br /> recommence. <br /> All required submittals shall be of sufficient detail and contain sufficient information to ensure <br /> that the proposed structure will be constructed in compliance with all adopted codes. <br /> Sincere/man <br /> Jeff He /v <br /> Development Technician <br />