Laserfiche WebLink
David Matthews <br />AuRu,;t 17, 1992 <br />Pagc Two of'L'hrec <br />S. As discussed in our pre-applicadnn review corridor 221 must be separated from the <br />open office area 212. <br />Twenty minute-rated door(s) swinging in the direction of exit Uavel could be used <br />with electronic hold-open devices to maintain an open feeling to this area if desired. <br />Door 59 is not required. <br />6. The stair handrails must be located 34 inches to 38 inches above the nosing of the <br />stair. <br />Rei:ent studies indicate that 38 inches is a safer height even for small children. <br />7. �xtion 1713(d) req�ires a thermal barrier betwcen foam plasdc insulation an� interior <br />spaces. <br />The G.W.B. illustrated would conform as a thermal barcier, however it must extend <br />to the underside of the floor or roof above (or to the top of the insulation). RE: Wall <br />Types 1, 3, 3A, 4, 4A, 4B. <br />8, Provide manufacturers informadon for the fireplace indicating the listing and required <br />clearances to combusdbles, hearth dimensions, flue requirements, venting <br />requirements, etc. <br />9. The occupant load of the dinin;/lounge area must be p�stcd per Section �302(c). <br />The maximum occupant load would be 299 based on tlie A3 occupancy classification <br />(the exit ways are capable of 506 occupants). <br />10. Provide accessible signage per Secdon 3103(b)4. <br />11. Provide grab bars and threshold at accessible showcrs per Section 3106(k)10. <br />12. Please provide details and elevations of rooftop mcchanical equipment scrccns <br />