Laserfiche WebLink
Rose Homes—Plan Check No. C0105-026 <br /> Page 5. <br /> 30. Show all safety glazing as required by Section 2406 of the UBC on the plans. <br /> Notations have been added to Sheet 2. <br /> 31. Note on plans: "Fire-blocking shall be provided in concealed spaces of stud <br /> walls and partitions, includingfurred spaces, at the ceiling and floor levels and at <br /> 10 foot intervals both vertical and horizontal and as specified in Section 708.2.1 i <br /> of the UBC. " <br /> This note has been added to Sheet 2. <br /> 32. Spec!&the type of weather protection for the roof. <br /> This has been added to Sheet 4. <br /> C33� Show attic ventilation calculations on the plan. Show required ventilation on <br /> // plans. Details shall be providedfor cross-ventilation of all vaulted ceiling <br /> construction. <br /> This has been added to Sheet 4. <br /> 34. Show stepped foundation on elevation views. <br /> Elevation views have been edited to show typical stepped foundation for this site, <br /> Sheet 1. <br /> 35. Provide detail for cripple wall construction in foundation. <br /> Cripple wall detail has been added to the elevation sheet, Sheet 1. <br /> 36. Provide the following on plans: <br /> • Minimum Soil Bearing Pressure <br /> • Equivalent Ruidpressure <br /> • Minimum concrete.strength <br /> • Minimum reinforcing bar grade <br /> • The wood grade and species of all framing lumber <br /> • The panel ID Index for plyHaod. <br /> • The design loads for the roof and floor. <br /> • The baric wind speed exposure <br /> • The Glu-Lam beam construction symbol and camber. <br /> JARNOT ENGINEERING INC. <br />