Laserfiche WebLink
i <br /> I <br /> 6. Please indicate the rise and run of the treads and the handrails on the existing stairs. <br /> it <br /> 7. The specific locations for required signage and lighting should be indicated on drawings,to include: <br /> • Existing and new illuminated exit signage at exits and exit access doors,per IBC 1011.1. <br /> • Existing and new emergency egress lighting,per IBC 1006.3. <br /> • Emergency(battery-operated)exterior lighting at exterior exits,per IBC 1006.3-5. <br /> • Tactile exit signs should be shown at the egress stairways and the exterior exit discharge doors, <br /> per IBC 1011.3. <br /> • Posted occupancy of tenant improvement in any single room with more than 50 occupants and <br /> the total occupancy should be posted inside of the main entrance,per Section 1004.3. <br /> 8. As this is a change of use,the toilet fixture count should be based on the new occupancy type per IBC <br /> Table 2902.1. <br /> Upon resubmission of the drawings,your application will be given priority and plan review will begin. All <br /> required submittals should be of sufficient detail and contain sufficient information 4o ensure that the proposed <br /> structure will be constructed in compliance with all adopted codes. Please provide a response letter,which <br /> shows where each item in this correction letter is addressed on the plan set. Peel free to drop by or call me with <br /> any questions at 425-257-8813. <br /> Sincerely, <br /> i <br /> Meg M. alcy <br /> Plans Examine <br /> s wsm�Nw•,enma as i i i sun s,,.0 e< lif/ <br />