TABLE C403.2.3(3)—continued <br /> MINIMUM EFFICIENCY REQUIREMENTS: <br /> ELECTRICALLY OPERATED PACKAGED TERMINAL AIR CONDITIONERS, <br /> PACKAGED TERMINAL HEAT PUMPS,SINGLE-PACKAGE VERTICAL AIR CONDITIONERS, <br /> SINGLE VERTICAL HEAT PUMPS,ROOM AIR CONDITIONERS AND ROOM AIR-CONDITIONER HEAT PUMPS <br /> EQUIPMENT TYPE SIZE CATEGORY SUBCATEGORY OR MINIMUM EFFICIENCY TEST e <br /> (INPUT) RATING CONDITION PROCEDURE <br /> Room air-conditioner <20,000 Btu/h — 9.0 EER <br /> heat pumps with <br /> louvered sides >20,000 Btu/h — 8.5 EER <br /> — <br /> Room air-conditioner <14,000 Btu/h — 8.5 EER <br /> heat pumps without ANSI/AIIA- <br /> louvered sides >14,000 Btu/h — 8.0 EER MRAC-1 <br /> Room air conditioner All capacities — 8.7 EER <br /> casement only <br /> Room air conditioner <br /> casement slider All capacities — 9.5 EER <br /> For SI: I British thenual unit per hour=0.2931 W,'C=[(°F)-32]/1.8. <br /> "Cap"=The rated cooling capacity of the product in Btu/h.If the unit's capacity is less than 7000 Btu/h,use 7000 Btu/h in the calculation.If the unit's <br /> capacity is greater than 15,000 Btu/h,use 15,000 Btu/h in the calculations. <br /> a. Chapter 6 of the referenced standard contains a complete specification of the referenced test procedure,including the referenced year version ofthe test <br /> procedure. <br /> b. Replacement unit shall be factory labeled as follows:"MANUFACTURED FOR NONSTANDARD SIZE APPLICATIONS ONLY:NOT TO BE <br /> INSTALLED IN NEW STANDARD PROJECTS"or MANUFACTURED FOR REPLACEMENT APPLICATIONS ONLY:NOT TO BE <br /> INSTALLED IN NEW CONSTRUCTION PROJECTS."Replacement efficiencies apply only to units with existing sleeves less than 16 inches(406 <br /> mm)in height and less than 42 inches(1067 mm)in width. <br /> TABLE 403.2.3(4) <br /> WARM AIR FURNACES AND COMBINATION WARM AIR FURNACES/AIR-CONDITIONING UNITS, <br /> WARM AIR DUCT FURNACES AND UNIT HEATERS,MINIMUM EFFICIENCY REQUIREMENTS <br /> EQUIPMENT TYPE SIZE CATEGORY(INPUT) SUBCATEGORY OR MINIMUM EFFICIENCYd,e, TEST PROCEDURE' <br /> RATING CONDITION <br /> Warm air furnaces,gas <225,000 Btu/h — 78%AFUE or,80%Er DOE 10 CFR Part 430 or <br /> s <br /> fired ANSI Z21.47 <br /> >225,000 Btu/h Maximum capacity` 80%Err ANSI Z21.47 <br /> Warm air furnaces,oil <225,000 Btu/h — 78%AFUE or 80%&r DOE 10 CFR Part 430 or <br /> fired UL 727 <br /> >225,000 Btu/h Maximum capacityb 81%Eis UL 727 <br /> Warm air duct fitrnaces' All capacities Maximum capacityb 80%Ec ANSI 283.8 <br /> gas fired <br /> Warm air unit heaters, All capacities Maximum capacityb 80%E, ANSI Z83.8 <br /> gas fired <br /> Warm air unit heaters, All capacities Maximum capacityb 800/oE, UL 731 <br /> oil fired <br /> For SI: 1 British thermal unit per hour=0.2931 W. <br /> a. Chapter 6 of the referenced standard contains a complete specification of the referenced test procedure,including the referenced year version ofthe test <br /> procedure. <br /> b. Minimum and maximum ratings as provided for and allowed by the unit's controls. <br /> C. Combination units not covered by the National Appliance Energy Conservation Act of 1987(NAECA)(3-phase power or cooling capacity greater than <br /> or equal to 65,000 Btu/h[19 kW])shall comply with either rating. <br /> d. E,=Thermal efficiency.See test procedure for detailed discussion. <br /> C. E,=Combustion efficiency(100%less flue losses).See test procedure for detailed discussion. <br /> Q1111 &=Combustion efficiency.Units must also include an IID,have jackets not exceeding 0.75 percent of the input rating,and have either power venting <br /> or a flue damper.A vent dam er is an acceptable alternative to a flue damper for those fianaces where combustion air is drawn from the conditioned <br /> space. <br /> r <br /> L�lIv4 \ I: <br /> g. E,=Thermal efficiency.Units must also include an IID,have jacket losses not exceeding 0.75 percent of the input rating,and have either power venting <br /> or a flue damper.A vent damper is an acceptable alternative to a flue damper for those furnaces where combustion air is drawn from the conditioned <br /> space. <br /> CE-42 2015 Washington State Energy Code �_ <br />