11, Supports for solar modules are Installed to spread the dead load across as many roof- -�_/ <br /> framing members as needed to ensure that no point load exceeds fifty(50)pounds, ❑ <br /> [iRC M2302.2.1(5)1 ' <br /> 12, The photovoltaic modules and supporting structure shall be constructed bf <br /> noncombustible materials or fire-retardant treated wood equivalent to that requiredfor 1/ ❑ <br /> the roof construction. [IRC M2302.2.1] <br /> 13, Roof and wall penetrations shall be flashed and sealed to prevent entry of water, �/ ❑ <br /> rodents,and insects.[IRC M2302,2.2] <br /> 14, PVmodules are listed and labeled with a fire classification In accordance with UL 1703. , ,/ ❑ <br /> [IRC M2302.2.3] '� <br /> Comments: <br /> ' =E If you answered yes to all of the above questions,the project qualifies for the over-the- <br /> coutiter permitting process. <br /> Determine if your project qualifies for an Over-the-Counter electrical permit <br /> Yes J No N/A <br /> 1. PV modules,Inverters,and combiner boxes are Identified for use In PV systems. ❑ <br /> 2, The inverters are listed and labeled in accordance with UL 1741 and are listed for IP/ ❑ <br /> utility interaction.[IRC M2302.41 <br /> El 02/ <br /> 3. The AC Interconnection point is on the load side of service disconnect. [NEC 690,64(B)l <br /> 4. The system meets all current NEC,City and Washington Cities Electrical Code 0 <br /> requirements, <br /> 5. For split-Buss modules the AC interconnection must be one of the six service <br /> disconnects. <br /> 6. Maximum load added to the panelboard is based on the rating of the panelboards bus/main OCPD <br /> combination in accordance with NEC 705,12(1))(2)(3)(b),and is limited to(check combination that <br /> applies): <br /> ❑225 amp bus/200 amp main OCPD-13,440 AC watts,maximum 70 amp inverter OCPD, <br /> 0225 amp bus/225 amp main OCPD- 8,640 AC watts,maximum 45 amp inverter OCPD. <br /> ❑200 amp bus/200 amp main OCPD- 7,860 AC watts,maximum 40 amp inverter CCPD, <br /> 11150 amp bus/150 amp main OCPD- 5,760 AC watts,maximum 30 amp inverter OCPD. <br /> ❑125 amp bus/125 amp main OCPD- 4,800 AC watts,maximum 25 amp inverter OCPD. <br /> ❑125 amp bus/100 amp main OCPD- 9,600 AC watts,maximum 50 amp Inverter OCPD. <br />