Laserfiche WebLink
7. Provide detail for rigid insulation in locations where insulation is above grade. Show <br /> how insulation is protected from impact and exposure to ultra-violet light. Show how <br /> insulation is flashed at siding. (R-15 is 3"thick?) <br /> 8. Provide fire blocking at concealed spaces at not more than 10"-0" O.C. horizontal & <br /> vertical (top of furred walls). <br /> 9. The "energy and ventilation" notes call out"R-15 where no exist. flatwork"at the floor <br /> edge. Rigid insulation is required (per proposed submittal) at the entire perimeter of the <br /> existing garage. (48 linear feet.) <br /> Please prepare a response letter showing where each item in this correction letter is <br /> addressed on the plan set. <br /> Upon resubmittal of the drawings, your application will be given priority and plan review will <br /> recommence. <br /> All required submittals shall be of sufficient detail and contain sufficient information to ensure <br /> that the proposed structure will be constructed in compliance with all adopted codes. <br /> Sincerely, <br /> Jeff Heilman <br /> Development Technician <br /> 425-257-8976 <br /> Email: iheilman@ci.everett.wa.us <br /> S:\1Common\Clerical\JHeilman\CW1204-008(5817 Lowell Rd 6-5-12).doc <br />