b. Rolled curbs shall be identified by red traffic paint with a 6-inch wide stripe on the curb, <br />extending the length of the designated fire lane. <br />C. Lanes without curbs shall be identified by red traffic paint with a 6-inch wide stripe on the <br />pavement, extending the length of the designated fire lane. <br />d. The words `NO PARKING — FIRE LANE' shall be in 3-inch stroke white letters 18 inches in <br />height, and placed 8 inches measured perpendicular from the red paint stripe on the pavement. <br />In most cases, both sides of the access road shall be marked. Where long drives are to be <br />marked, the repetitions shall alternate sides of the drive. <br />e. Marking shall also include the addition of metal signs stating `NO PARKING — FIRE LANE <br />— TOW AWAY ZONE — EMC 46.28.130' to be installed at intervals or locations designated <br />by the Fire Code Official. The signs shall be approximately 12 inches in width and 18 inches <br />in height and have red letters on a white background. Metal signs shall be installed on 2-inch <br />metal pipes for private or public property and shall be located so that the bottom of the sign is <br />a minimum of 7 feet above the curb. Where fire lanes are adjacent to buildings or structures <br />and when approved or directed by the Fire Code Official, the signs may be placed on the face <br />of the building or structure. <br />f. Where directed by the Fire Code Official, specific areas shall be designated and those areas <br />are to be marked with diagonal striping across the width of the fire lane. Diagonal marking <br />shall be used in conjunction with painted curbs and/or edge striping and shall run at an angle <br />of 30 to 60 degrees from one side to the other. These diagonal lines shall be in red traffic <br />paint, parallel with each other, at least 6 inches in width and 24 inches apart. Lettering shall <br />appear as above. <br />4. Premise Identification - Premises shall be clearly identified by the correct address at the street entry. <br />Buildings shall be clearly identified so as to be visible and legible from the access road. Individual <br />apartments and suites, where applicable, shall be clearly and legibly identified from the access road. <br />See EMC 16.03, Section 505.1.1 (Address Posting Policy). <br />10-inch numbers are required on the building. <br />5. Fire Hydrants - Locations as planned are acceptable. <br />6. Fire flow for this project is 1,500 gpm. <br />7. Portable Fire Protection - A portable fire extinguisher with a minimum U.L. rating of <br />2-A:10-B:C shall be provided within 75 feet of travel on all floors of each building during <br />construction and prior to occupancy. <br />Kitchens - Install a K-type fire extinguisher within 30 feet of the grill and deep fryers. <br />9. Commercial Cooking Operations - A ventilating hood and duct system with an approved automatic <br />fire -extinguishing system shall be provided in accordance with the Mechanical Code for commercial - <br />type food heat -processing equipment that produces grease -laden vapors. <br />10. Fire Alarm S, sy tem - An approved automatic fire detection system shall be provided as required by <br />City Ordinance No. 3021-07, Chapter 16.76, of the Everett Municipal Code. <br />Plans for such system shall be submitted to the Fire Code Official for review and approval prior to <br />installation. Submittal shall include cut sheets of equipment intended for use. Appropriate trip <br />6 <br />Final MDNS S #16-005 <br />