gEmacm <br /> 2012 Washington State Energy Code Compliance Forms for Commercial,Group R1,and>3 story R2 and R3 Revised June 2013 <br /> Project Address 801 Wetmore Ave-EvCC Olympus Hall HVAC Date 1/25/2016 <br /> The following information is necessary to check a mechanical permit application for commercial provision compliance with the 2012 <br /> WSEC. NOTE:Define print area in Excel prior to printing MECH-CHK pages. <br /> Applicability Code Section Code Provision Information Required Location Building Department <br /> (yes,no,na) I I on Plans Notes <br /> COMPLEX SYSTEMS,CONTINUED <br /> Specific System Requirements <br /> y C403.4.2& Variable flow control-fans Indicate fans requiring variable flow control and method <br /> C403.2.12 MO.2 <br /> NA C403.4.2.1 VAV fan static pressure Indicate sensor locations on plans;include at least one sensor per major - <br /> sensors duct branch <br /> C403.4.2.2 VAV fan static pressure Indicate fan system static pressure setpoint based on zone requiring most <br /> NA setpoint pressure - <br /> VAV systems serving multi- Indicate supply air systems serving multiple zones that are required to be <br /> C403.4.5 VAV,method of primary air control,and zones served;note exceptions <br /> NA zones taken MO.2 <br /> y C403.4.5.4 VAV system supply air reset Indicate controls that automatically reset supply air temp in response to MO.1 <br /> loads <br /> NA C403.4 Large capacity cooling Indicate method of multi-stage or variable control for building cooling <br /> systems system capacity>300 tons <br /> NA C403.4.7 Hot gas bypass limitation Indicate cooling equipment unloading or capacity modulation method _ <br /> y C403.4.3 Large capacity boiler Indicate multi-stage or modulating burner for single boilers>500,000 btuh <br /> systems MO.2 <br /> y C403.4.3 Boiler sequencing Indicate automatic controls that sequence operation of multiple boilers MO.2 <br /> C403.4.3.5 Chiller/boiler plant pump Indicate capability to automatically reduce overall plant flow and shut-off <br /> y isolation flow through chillers&boilers when not in use MO.2 <br /> C403.4.2& Variable flow control- Indicate pumps requiring variable flow control&method <br /> y C403.4.3.6 pumps MO.2 <br /> NA C403.2.12.1 Variable flow control- Indicate cooling tower fans requiring variable flow control and method _ <br /> &C403.4.4 cooling towers <br /> C403.4.3.4 Hydronic system part load reset supply water tem AND reduce flow b >50%fors stems>300,000 <br /> y controls PP y P y- y Mo.1 <br /> NA C403.4.3.2Two-pipe changeover Indicate deadband,heating/cooling mode scheduling and changeover <br /> systems temperature range <br /> NA C403.4.3.3.1 Water loop heat pump- Indicate capability of central equipment to provide min.20°F water supply <br /> deadband temp deadband between heat rejection and heat addition modes <br /> NA C403.4.3.3 Water loop heat pump- Provide heat exchanger that separates cooling tower and heat pump loop - <br /> heat rejection in Climate Zone 5 <br /> NA C403.4.3.3.3 Water loop heat pump- Indicate 2-way isolation valve on each heat pump and variable flow control - <br /> isolation fors stems with total pump power>10 h <br /> NA C403.4.6 Condenser water heat Indicate system provided to pre-heat service water and efficiency _ <br /> recovery <br /> N A C403.5 Cooler/freezer-anti-sweat Indicate w/sf&control method for walk-in cooler/freezer door anti-sweat - <br /> heaters I heaters <br /> NA C403.5/6 Cooler/freezer-evaporator Indicate motor type for evaporator and condenser fans<1 hp - <br /> a dco n rfans <br /> SERVICE WATER HEATING <br /> Service Water Systems <br /> NA C404.2 Water-heating equip min. Provide equipment schedule or complete MECH-SUM table with type, <br /> efficiency capacity,efficiency,test standard or other efficient source <br /> NA C404.3 Temperature controls Indicate temperature controls have required setpoint capability <br /> N A C404.4 Heat traps Indicate piping connected to equipment have heat traps on supply& <br /> discharge <br /> NA C404.5 Insulation underwater Indicate R-10 insulation under tank _ <br /> heater <br /> NA C404.6 Service water piping Indicate R-value of insulation on piping;note exceptions taken <br /> insulation <br /> C404.7/8 Circulation systems and Indicate shut-off capability based on occupancy and periods of limited <br /> NA heat trace shut-off demand _ <br /> NA C404.9 Group R-2 service hot water Indicate method of usage metering for dwell.units served by central HW <br /> eters s <br /> Pools&In-Ground Permanently Installed Spas <br /> Pool heating equip min. Provide equipment schedule or complete MECH-SUM table with type, <br /> NA C404.10.1 efficiency capacity,efficiency,test standard(or other eff.source);heat pump heaters <br /> >_4 COP <br /> NA C404.10.1/2 Pool heater on/off controls Indicate automatic on/off control based on scheduling&accessible on/off <br /> switch on heater that operates independent of thermostat setting;or <br /> NA C404.10.3 Pool covers Indicate vapor retardant cover and insulation rating as required _ <br /> NA C404.10.3 Pool assembly insulation Indicate rating of insulation on sides and bottom of pools heated to>90°F <br /> NA L.C404.10.4 Heat recovery Indicate method,exhaust air temperature reduction and recovered energy - <br /> us <br />