Laserfiche WebLink
pressure set point equals 1/3 the total design static C403.3 Economizers(Prescriptive).Air economizers <br /> pressure,and 50 percent of design water flow for shall be provided on all new systems including those <br /> pumps,based on manufacturer's certified test data. serving computer server rooms,electronic equipment, <br /> Variable inlet vanes,throttling valves(dampers), radio equipment,and telephone switchgear.Economizers <br /> scroll dampers or bypass circuits shall not be allowed. shall comply with Sections C403.3.1 through C403.3. 4. <br /> Exception:Variable speed devices are not Exception:Economizers are not required for the <br /> required for motors that serve: systems listed below: <br /> 1. Fans or pumps in packaged equipment where 1. Systems complying with Section C403.6 <br /> variable speed drives are not available as a Dedicated outdoor air systems(DOAS)with <br /> factory option from the equipment year-round cooling loads from lights and <br /> manufacturer. equipment of less than 5 watts per square foot. <br /> 2. Fans or pumps that are required to operate 2. Unitary or packaged systems serving one zone <br /> only for emergency fire-life-safety events with dehumidification that affect other systems <br /> (e.g.,stairwell pressurization fans,elevator so as to increase the overall building energy <br /> pressurization fans,fire pumps,etc.). consumption.New humidification equipment <br /> shall comply with Section C403.2.3.4 <br /> C403.2.13.1 Heat rejection equipment.The 3. Unitary or packaged systems serving one zone • <br /> requirements of this section apply to heat rejection where the cooling efficiency meets or exceeds <br /> equipment used in comfort cooling systems such as the efficiency requirements in Table 0403.3. <br /> air-cooled condensers,open cooling towers, <br /> closed-circuit cooling towers,and evaporative 4. Water-cooled refrigeration equipment serving <br /> condensers. chilled beams and chilled ceiling space cooling <br /> Exception:Heat rejection devices included as an systems only which are provided with a water <br /> integral part of equipment listed in Tables economizer meeting the requirements of Section <br /> C403.2.3(1)through C403.2.3(3). C403.3.4. <br /> Heat rejection equipment shall have a minimum 5. Systems complying with all of the following <br /> efficiency performance not less than values specified criteria: <br /> in Table C403.2.3(8).These requirements apply to all 5.1. Consist of multiple water source heat <br /> propeller,axial fan and centrifugal fan cooling pumps connected to a common water loop. <br /> towers.Table C403.2.3(8)specifies requirements for 5.2. Have a minimum of 60 percent air <br /> air-cooled condensers that are within rating economizer. <br /> conditions specified within the table. 5.3. Have water source heat pumps with an • <br /> C403.2.13.1.1 Variable flow controls.Cooling EER at least 15 percent higher for cooling <br /> tower fans 7.5 hp and greater shall have control and a COP of at least 15 percent higher for <br /> devices that vary flow by controlling the leaving heating than that specified in Section <br /> fluid temperature or condenser C403.2.3. <br /> temperature/pressure of the heat rejection device. 5.4. Where provided,have a central boiler or <br /> 0403.2.13.1.2 Limitation on centrifugal fan furnace efficiency of 90 percent minimum <br /> cooling towers.Open cooling towers with a for units up to 199,000 Btu/h. <br /> combined rated capacity of 1,100 gpm and greater 5.5. Provide heat recovery with a minimum 50 <br /> at 95°F condenser water return,857 condenser percent heat recovery effectiveness as <br /> water supply and 75'F outdoor wet-bulb defined in Section C403.5 to preheat the <br /> temperature shall meet the energy efficiency outside air supply. : <br /> requirement for axial fan open circuit cooling 6. For Group R occupancies,cooling units installed <br /> towers. outdoors or in a mechanical room adjacent to <br /> C403.2.14 Electric motor efficiency.Electric motors, outdoors with a total cooling capacity less than <br /> including fractional hp motors,shall comply with the 20,000 Btu/h and other cooling units with a total <br /> provisions of Section C405.8. cooling capacity less than 54,000 Btu/h provided . <br /> that these are high-efficiency cooling equipment <br /> with IEER,SEER,and EER values more than 15 <br /> percent higher than minimum efficiencies listed <br /> in Tables C403.2.3 (1)through(3),in the <br /> appropriate size category,using the same test <br /> 2015 Washington State Energy Code CE-59 <br /> 3�� <br />