- . . . . . . . . . . . . . . . . . . . . . . . . . <br /> 3. RISER/BLOCK DIAGRAM <br /> FAA FACP <br /> O2 3 NAC NAC <br /> ® 7 7 <br /> SLC 9 9 <br /> 5 6 7 8 <br /> SLC <br /> NOTES(CLASS B SYSTEM): <br /> OREPLACE EXISTING DEVICE WITH NEW. RE-USE EXISTING <br /> SYSTEM WIRING. <br /> O120VAC MAIN POWER FOR THE FIRE ALARM SYSTEM (RE-USE <br /> EXISTING). THIS SYSTEM REQUIRES A DEDICATED CIRCUIT <br /> THAT IS LABELED. "FIRE ALARM CIRCUIT'AND IS ACCESSIBLE <br /> ONLY TO AUTHORIZED PERSONNEL. <br /> OCIRCUIT BREAKER LOCATION(S) SHALL BE PERMANENTLY <br /> NOTED AT ALL FIRE ALARM PANELS <br /> ®(2) PHONE LINES TO RJ-31 X TELCO BLOCKS (RE-USE EXISTING) <br /> WITHIN 30F FACP <br /> ODETECTORS: DUCT SMOKE TYPE,SMOKE, HEAT... <br /> © MONITOR MODULES: INPUTS FOR CONVENTIONAL TYPE <br /> DEVICES, WATERFLOW,SPRINKLER SUPERVISORY,HVAC, <br /> ELEVATOR, CRITICAL PROCESSES... (47K OHM EOLR AT LAST <br /> DEVICE) <br /> ORELAY/SIGNAL MODULES: OUTPUTS FOR HVAC, ELEVATOR, <br /> CRITICAL PROCESSES, REMOTE NAC PANEL ACTIVATION <br /> ® MANUAL PULL STATIONS <br /> OFIELD NOTIFICATION DEVICES (STROBES, HORNS) EOLR AT <br /> LAST DEVICE <br />