. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . - - - - . . - - - - - - - - . <br /> 4. BATTERY CALCULATIONS <br /> i 01 OOOG <br /> Q . Source Description Stbv each Alm each Standbvl Alorm I <br /> 1 101000 FIRE ALARM CONTROL PANEL 0.172 0.267 <br /> - STANDARD LOOP(SLC 1) 0.045 0.115 <br /> 1 iO-SDCI EXPANDER LOOP(SLC2) 0.055 0.080 <br /> iO-SDC2 EXPANDER LOOPS 2(SLC3 and SLC4)NOT USED <br /> 2 SIGA-CCI signal module 0.000223 0.000100 0.000446 0.000200 <br /> 55 SIGA-PS photoelectric smoke detector 0.000045 0.000045 0.002475 0.002475 <br /> 4 SIGH-HRS fixed/rate of rise heat detector 0.000045 0.000045 0.000180 0.000180 <br /> 11 SIGA-278 manual pull station 0.000250 0.000400 0.002750 0.004400 <br /> 1 SA-DACT DUAL IN-LINE DIALER 0.041 0.100 <br /> I RLCD-C REMOTE ANNUNCIATOR 0.099 0.115 0.099 0.115 <br /> NAC/AUX-1 NAC TRIGGER 1.500 <br /> NAC/AUX-2 SPARE 0.000 <br /> NAC/AUX-3 SPARE 0.000 <br /> NAC/AUX-4 SPARE 0.000 <br /> TOTAL 0 418 2.184 <br /> 20%Efficiency Factor 1.2 1.2 <br /> 24 Standby Hour Required Ah Required for Stby 12.034 <br /> S Alarm Minutes Required Ah Required for Alm 0.218 <br /> Total Ah required for cabinet 12.253 <br /> Battery Capacity Supplied (2)18Ah <br />