Laserfiche WebLink
Third Floor <br /> Plumbing: <br /> 1. The kitchen sink is back graded and accordion tailpieces are not allowed. <br /> Mechanical: <br /> 1. The Type II hood over the stove is not piped to the outside. <br /> 2. The heat ducts are not sealed and some are disengaged and blowing air into the wall <br /> cavity. <br /> 3. The heat ducts in the attic are not fully insulated to a minimum of R-8. <br /> 4. The gas appliance flex connector to the furnace in the attic cannot penetrate the furnace <br /> housing. See 411.1.3.3 IFGC <br /> 5. The B-vent termination through the roof is at an angle with the vent cap half off. The <br /> vent cap is there to keep out moisture, debris and animals; it also prevents wind <br /> interference that could negatively affect the vent's ability to produce the required draft. <br /> See 503.6.6 IFGC. <br />