2015 Washington State Energy Code Compliance Forms far Commercial,R2 and R3 over 3 stories and all R1-Page 3 Of 7
<br /> Mechanical Permit Plans Checklist I�
<br /> 2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2&R3 aver 3 stories and all R1 Revised January 2017
<br /> Project Title: JOS T.I. Cate 2/2/2027
<br /> The following information is necessary to check a permit application for compliance with the mechanical systems and equipment requirements of the
<br /> Washington State Energy Cade,Commercial Provisions.
<br /> Applicable Code Section Cade Provision Information Required-Must be in permit documents Location in Building Department
<br /> (Applicable
<br /> Documents Notes
<br /> C403.2.4.10 Group R2/R3 dwelling For primary space conditioning system,indicate 5-2 programmable thermostats capable of two
<br /> NA C403.2.4.11 units,Group R2 sleeping setback periods per day;for all thermostats indicate purpose(heating only,cooling only,or
<br /> units both),required temperature range and at minimum a 10°F deadband;or exception taken
<br /> Indicate method of ventilation air delivery(natural or mechanical)for each zone M-C
<br /> - --- __...._..._.. - ....
<br /> ..............._.-........------..------___......---...._._..... --- — -
<br /> If mechanically delivered,indicate that systems are configured to provide not more than 150% M-C
<br /> Yes C403.2.6 Ventilation of,but at least the minimum required volume of outdoor air to each zone per IMC,ASHRAE
<br /> C403.2.11 A 62.1 or other applicable code(WAC,OSHA,etc);or exception taken
<br /> If delivered via natural ventilation,identify required elements per IMC including minimum
<br /> openable area to the outdoors or qualifying adjoining spaces
<br /> Identify spaces>500 sf with occupant load>25 people/1,000 sf per IMC:for each space
<br /> NA C403.2.6.2
<br /> Demand controlled Indicate whether it is served by an HVAC system with total design OSA>3,000 cfm,and/or
<br /> ventilation the system has airside economizer or automatic modulating OSA damper;indicate OSA
<br /> controls are configured to provide demand controlled ventilation or provide supporting
<br /> documentation for applied exception
<br /> For gyms,classrooms,auditoriums and conference rooms>500 at,indicate occupancy-based
<br /> NA C403.2.6.3 Occupancy sensors OSA control when space is unoccupied and method(closes OSA damper or shuts-off
<br /> equipment);or aftemate means provided to automatically reduce OSA when space is partially
<br /> occupied
<br /> C403.2.6.4 Enclosed loading dock For enclosed loading docks,indicate ventilation/exhaust system method of activation(gas
<br /> NA C403.2.6.4.1 ventilation detection system for CO and NO2,or occupancy sensors),and control method(staged or
<br /> modulating)
<br /> NA 0403.2.6.4 Enclosed parking garage For enclosed parking garages,indicate ventilation/exhaust system activated by gas detection
<br /> C403.2.6.4.2 ventilation system for CO and NO2,and control method(staged or modulating);or exception taken
<br /> Provide calculations that show a balanced accounting of total kitchen exhaust(include all
<br /> hoods)with%of:supply air,transfer air from adjacent spaces,and make-up air,if applicable,
<br /> NA C463.2.7.1 l(itchen exhaust hoods indicate that direct make-up air to each hood does not exceed 10%of hood exhaust
<br /> ----s with total ---'------ ----- -
<br /> For kitchens with iota)hood exhaust exceeding 2.009 dm,indicate exhaust air rate per Table
<br /> C403.2.7.1 and compliance method(DCV,energy recovery,or transfer air that would
<br /> otherwise be exhausted)
<br /> NA C403.2.7.2 Laboratory exhaust systems Refer to Systems Requiring Energy Recovery for requirements
<br /> Variable flow capacity- For HVAC fan motors a 7.5 hp,indicate method of variable flow control(VSD,or equivalent
<br /> NA 0403.2.13 HVAC system fans control method that reduces design air volume by 50%at 113 static design pressure);note
<br /> exception taken
<br /> OX air handler variable For DX air handlers with economizer and cooling capacity 2:65,000 Btuth,indicate number of
<br /> cooling control cooling stages provided and method(multiple compressors and i or variable speed
<br /> NA C403.3.1 compressors);indicate minimum displacement(capacity reduction)as%of full load
<br /> (Under integrated ----._._..--- —-....... ---......... ----...
<br /> Economizer) Indicate control method(cooling capacity controlled in response to space temperature,space
<br /> temperature controlled by modulating supply airflow,or both)
<br /> For DX air handling units with cooling capacity L 65,000 Btu/h and evaporative and chilled
<br /> water air handling units with fan 2 0.25 hp,indicate whether system is single zone or multiple
<br /> zone and related control method(cooling capacity controlled in response to space
<br /> temperature,space temperature is controlled by modulating supply airflow,or both)
<br /> ----_ ----- ---- — — ----....,_. ..----.... -----. — -- ---- -- ---
<br /> For mechanical cooling systems(Includes DX and chiliad water coils)that- control.
<br /> ro..ofing
<br /> capacity in response to space temperature-Provide a minimum of two stages of fan control;
<br /> NA C403.2.11.5 Fan airflow control indicate minimum fan speed is s 66%of full speed drawing15 40%of full speed fan power
<br /> during periods of low cooling or ventilation only
<br /> For other mechanical cooling systems(includes DX and chilled water coils)that control space
<br /> temperature by modulating airflow(in lieu of,or in addition to,controlling capacity in response
<br /> to space temperature)-Provide fan controls for modulating supply airflow;indicate minimum
<br /> fan speed is$50%of full speed drawing 5 30%of full speed fan power during periods of low
<br /> cooling or ventilation only;or exception taken
<br /> Provide central and zone level DOC controls as required based on system application,
<br /> NA C403.2.4.12 DDC system capabilities capacity cr size thresholds and other qualification per Table C403.2.4.12.1
<br /> Identify all DDC system input/output control points;indicate capability for trending and
<br /> ra hical display
<br /> Ducting Systems
<br /> 0403.2.8.1 indicate on plans that all ductwork is constructed and sealed per IMC M-C
<br /> Yes Duct construction -----... --- --.... ----- ---._...... -----------•-- - ------ --- _....-----
<br /> C403.2.8.3 For OSA ductwbrk,also indicate on plans that ductwork meets air leakage requirements per
<br /> 0402.5 and vapor retarder requirements per the IBC M-C
<br /> Yes C403.2.8.3 Duct pressure Identify location of low,medium and high pressure ductwork on plans
<br /> ctassiFlcations tit-C
<br /> NA C403.2.8.3.3 High pressure duct leakage Indicate high pressure duct leakage testing requirements on plans;provide test results to
<br /> lest ijurisdicfion when completed
<br />
|