Laserfiche WebLink
r <br /> shall specify the heating equipment type and shall show the location of the heating and <br /> cooling equipment and all ductwork. <br /> 6. All stairways are required to have a minimum 36" landing at the top and bottom. <br /> Provide 36" landing at bottom of stairs leading into the garage. <br /> 7. The Storage Room that is accessed from the garage appears to be at the same floor <br /> level as the garage. The foundation plan shows a crawl space at this location. Please <br /> clarify. <br /> 8. The wall between the garage and the Hall, Laundry, and Storage Room is required to be <br /> insulated to minimum R-21. The existing wall is 2 x 4 construction, which will not <br /> accommodate -21 insulation. <br /> 9. The insulation in the floor joists shall be in contact with the heated floor and <br /> permanently supported at not more than 24"o.c. <br /> 10. The attic insulation baffle shall extend 6"vertically above batt insulation and minimum <br /> 12"above loose-fill insulation. Show on plans. <br /> Please prepare a response letter showing where each item in this <br /> correction letter is addressed on the plan set. <br /> Upon resubmittal of the drawings, your application will be given priority and plan review will <br /> recommence. <br /> All required submittals shall be of sufficient detail and contain sufficient information to ensure <br /> that the proposed structure will be constructed in compliance with all adopted codes. <br /> Sincerely, <br /> Jeff Heilman <br /> Development Technician <br /> 425-257-8976 <br /> Email: jheilman@ci.everett.wa.us <br /> S:\lCommon\Clerical\]Heilman\C1507-004(10820 1st DR SE).doc <br />