Laserfiche WebLink
� � � <br /> TABLE C403.2.3(3)—continued <br /> MINIMUM EFFICIENCY REQUIREMENTS: <br /> ELECTRICALLY OPERATED PACKAGED TERMINAL AIR CONDITIONERS, <br /> PACKA�GED TERMINAL HEAT PUMPS,SINGLE-PACKAGE VERTICAL AIR CONDITIONERS, <br /> SINGLE VERTICAL HEAT PUMPS,ROOM AIR CONDITIONERS AND ROOM AIR-CONDITIONER HEAT PUMPS <br /> EQUIPMENT TYPE SIZE CATEGORY SUBCATEGORY OR MINIMUM EFFICIENCY TEST <br /> (INPU� RATING CONDITION PROCEDUREa <br /> Room air-conditioner <20,000 Btu/h — 9.0�l:R <br /> heat pumps with �2o 000 Btu/h — 8.��LI2 <br /> louvered sides — <br /> Rooin air-conditioner <14,000 Bhi/h — 8.5 EPR <br /> heat pumps without >14,000 Btu/h — 8.0 i:�R ANSUAHA- <br /> louvered sides — MI2AC-1 <br /> Room air cotlditioner AII caip�citics — 8.7 CL;R <br /> casemcnt only <br /> Room air conditioner All capacities — 9.�ELR <br /> casement-slider <br /> Por SI: 1 British thennal unit per hour=02931 W,°C=[(°F)-32]/1.8. <br /> "Cap"=The rated coolin�capaciry of the product in Btu/li.If the unit's capacity is less than 7000 Blu/h,use 7000 BtuM in thc calculation.If the unit's <br /> capacity is greater than 15,000 Btu/h,use 15,000 Btu/h in the calculations. <br /> a. Chapter 6 of the referenced standard contains a complete specification of the referenced test procedure,including the referenced year version of the test <br /> procedure. <br /> b. Replacement unit shall Ue factory labeled as follows:"MANIJFACTURED FOR NONSTANDARD SIZE APPLICATIONS ONLY:NOT TO BE <br /> INSTALLED IN NEW STANDAR.D PROJECTS"or MAIvTUFACTURED FOR REPLACEMENT APPLICATIONS ONLY:NOT TO BE <br /> INSTALLED N NEW CONSTRUCTION PROJECTS."Replacement efficiencies apply only to units with existing sleeves less than 16 inches(406 <br /> mm)in height and]ess than 42 inches(1067 mm)in width. <br /> TABLE 403.2.3(4) <br /> WARM AIR FURNACES AND COMBINATION WARM AIR FURNACES/AIR-CONDITIONING UNITS, <br /> WARM AIR DUCT FURNACES AND UNIT HEATERS,MINIMUM EFFICIENCY REQUIREMENTS <br /> EQUIPMENT TYPE SIZE CATEGORY(INPUT) SUBCATEGORY OR MINIMUM.EFELCIENCYd'e, TEST PROCEDUREa <br /> RATING CONDITION <br /> ,_ � <22�,000 Btu/h — 78%AFUE or 80%L'�` DOI;10 CFR Part 430 or <br /> Warm air furnaces,gas ANSI Z21.47 <br /> fired . <br /> >225,000 Btu/h Maximum capacity` 80%L'� ANSI Z21.47 <br /> <225,000 Btu/li — 78%APU�or 80%E�` DOE 10 CFR Part 430 or <br /> Warm air fi�rnaces,oil UL 727 <br /> fired UL 727 <br /> >225,000 Btu/h Maximum capacity� 81%E�s <br /> Wann air duct furnaces, All capacities Maximum capacitye 80%E� ANSI 183.8 <br /> gas fired <br /> W�rm air unit heaters, All ca�acities Maximum ca acit � 80%E� <br /> gas fired E p Y ANSI'L83.8 <br /> Warm air unit heaters, All capacities Maximum capacitye 80%E� UL 731 <br /> oil fired <br /> Por SI: 1 Britisli thermal unit per liour=02931 W. <br /> a. Chapter 6 of the referenced standard contains a complete specification ofthe refercnced test procedure,includii�g the referenced year version of the test <br /> procedure. <br /> b. Minimum and maximum ratin�s as provided for and allowed by the uniYs controls. <br /> c. Combinatio�i units not covered by the National Appliance�nergy Co��servation Act of 1987(NA�CA)(3-phasc power or cooling capacity greater than <br /> or equal to 65,000 Bhi/h[19 kW])shall comply with either rating. <br /> d. E�=Themial efficiency.Sce test procedure for detailed discussion. <br /> e. E�=ComUustion efficiency(100%less flue losses).See test proccdure for detailed discussion. <br /> f. L'�=Combustion efficicncy.Units must also includc an IID,havejackets not exceeding 0.75 percent ofthc input rating,and have either powcr venting <br /> or a flue damper.A vent damper is an acceptable altcrnative to a flue damper for ihose fimiaces���here combustion air is dra��ni from the conditioned <br /> space. <br /> g. E�=Thermal efficiency.Units must also include an IID,have jacket losses not excecding 0.75 percent of the input ratine,and have either power venting <br /> or a fluc damper.A vent damper is an acceptable alternative to a iluc damper far those furnaces where combustion air is drawn from thc conditioned <br /> space. <br /> CE-42 2015 Washington State Energy Code <br /> � �! <br />