Laserfiche WebLink
Psychrometrics - Zone Default <br /> Calculation Month: July Calculation Hour: -4:00 p.m. <br /> Air Conditions Loads(Btu/h) <br /> Airflow Humidity Ratio <br /> (CFA� Dry Bulb Wet Bulb <br /> Temperature Temperature ��bs of moisture/ Total Sensible Latent <br /> Ib of dry air) <br /> Outside Air 7,470 81'F 66.13° F 0.01031 8�1,900 �38,300 36,500 <br /> Return Air at Diffusers 29,700 83.74"F 69.67° F 0.012-14 <br /> Return Duct Leakage (0°G�)0 <br /> Return Duct Temperature Gain +0'F 0 0 0 <br /> Return Air at Aparatus 29,700 83.74°F 69.67°F 0.012-4a <br /> Mixed Air 37.200 83.19°F 68.89°F 0.01201 <br /> Coil llew Point 31.60O 49.81'r 49.81°F O.OU76? <br /> Coil Bypass Air (15%)5.57O 83.19"F 68.89° F 0.01201 <br /> Coil Leaving Air 37,Z0O Sd.82�'F 53.11' F 0.00828 <br /> System Load 1,030,000 1,120,000 -98,200 <br /> Reheat +0°F <br /> Humidification 0.00431 <br /> Fan(Draw'1'hrough,2 HP) +0.13°F 5,090 5,090 0 <br /> Motor(In Airstream,70% Efficient) +0.05°F 2,180 2,180 0 <br /> Supply Duct Leakage (0%)0 <br /> Supply Duct Temperature Gain +0° F 0 0 0 <br /> Supply Air at Diffusers 37,200 55°F 55°F O.O1260 <br /> Room Load -O.OQ016 ],120,000 1,150,000 -27,900 <br /> Final Room Conditions 83.74' F 69.67�F 0.01244 <br /> T <br /> ��; <br /> � <br /> ,�3 <br />