Laserfiche WebLink
� Psychrometrics - Zone Conditioned <br /> Calculation Month: July Calculation Hour: a:00 p.m. <br /> Air Conditions Loads(Btu/h) <br /> Airflow Humidity Ratio <br /> (CFM) Dry Bulb Wet Bulb <br /> Temperature Temperature ��bs of moisture/ Total Sensible Latent <br /> Ib of dry air) <br /> Outside Air 1,440 81°F 66.13°F 0.01031 16,400 9,310 7,040 <br /> Return Air at Diffusers 5,200 75°F 62.4°F (1.00929 <br /> Return Duct Leakage (0%)0 <br /> Return lluct Temperature Gain +0°F 0 0 0 <br /> Return Air at Aparatus 5,200 7S°F 62.4°F 0.00929 <br /> Mixed Air 6,640 763°F 63.19°F 0.009j 1 <br /> Coil Dew Point 5,640 S0.p5°F 50,05°F 0.00769 <br /> Coil Bypass Air (15°/r�)996 76.3°F 63.19°F 0.00951 <br /> Coil Leaving Air 6,640 53.98'F 523'F 0.00796 <br /> System Load 182,O00 155,000 27,800 <br /> Reheat +0�F <br /> Humidif'ication Q00068 <br /> Fan(Draw Through,2 HP) +0.71°F 5,090 5,090 0 <br /> Motor(In Airstream,70% Efticient) +0.3°F 2,180 2,180 0 <br /> Supply Duct Leakage (0�7�)0 <br /> Supply Duct Temperature Gain +0°F 0 0 0 <br /> Supply Air at Diffusers 6,640 55°F 53.93°F 0.00865 <br /> Room Load 0.00065 167,000 146.000 20,800 <br /> Final Room Conditions 75°F 62.4°F 0.00929 <br /> �3� �3 �,�' <br /> � <br />