Laserfiche WebLink
� � <br /> apartments and st�ities, where applic�ble, sball bc clearly atld le�ibly identified fram the access road. See <br /> �MC 16.03, Section 505.1.1 (Address Posting Policy). <br /> 16-inch numbers shall be used on the top corner of the building; 8-inch numbers shall be used over the <br /> lobby entrance. <br /> 8. Fire H. dY rants - Locations as planned are acceptable. <br /> 9. Fire flow for this project is 1,750 gpm. <br /> 10. Portable Fire Protection - A portable fire extinguisher with a minimum U.L. rating of <br /> 2-A:10-B:C shall be provided within 75 feet of travel on all floors of'each building during construction <br /> and prior to occupancy. <br /> 11. Fire Alarm System - An approved automatic fire detection system shall be provided as required by City <br /> Ordinance No. 3021-07, Chapter 16.76, of the Everett Municipal Code. <br /> Plans for such system shall be submitted to the Fire Code Official for review and approval prior to <br /> installation. Submittal shall include cut sheets of all equipment intended for use. Appropriate trip tests, <br /> witnessed by a Fire l�epartment Tnspect�r, sh�ll be perFormed. al�n�with a certificate �f completion, <br /> prior to tinal acceptance of the system. <br /> Fire alarm systems shall be installed according to NFPA Chapter 72, 2010 Edition. Installation of fire <br /> alarm coinponents, including basic wiring, may not commence before plans are approveci by the <br /> Fire Department Plan Reviewer. Fire alarm drawings must be professionally rendered, in sufficient <br /> detail, and must be internally consistent. Riser diagrams must match installation plans and load <br /> calculations. Components must be listed and approved for use together. Changes to plans must include <br /> new drawings and calculations and must be approved by the Fire Department Plan Reviewer prior to <br /> installation. Fire alarm installation is subject to field inspection by a Fire Department Inspector. An <br /> approved set of plans and the Engineering &Public Services Depai-tment electrical permit must be <br /> present for any installation inspection. <br /> 1{'ire alarm systems shall be installed under permit of the City of Everett Engineering & Public Services <br /> Department. Electrical inspections and approval are required prior to calling for acceptance tests. Call <br /> (425) 257-8810 for pennit information. <br /> The absence of monitoring for the alarm system will be cause for postponing Fire Department <br /> inspection and testing and shall result in denial of occupancy. <br /> A copy of NFPA 72 Record of Completion fonn must be filled out prior to final occupancy (NFPA 72, <br /> 2010 Edition, Chapter 10, page 114). <br /> Call for design requirements per Authority Having Jurisdiction. <br /> Automatic smoke detection is required. <br /> 12. If needed, for buildinbs with two or more floors, including sub-floors, the alarm system must call point- <br /> by-point reporting to an alarm center. � ` <br /> .$�, � � <br /> FINAL MDNS SrPA#16-008 � � ' <br />