• <br /> M Y <br /> KirklandDynamics <br /> Code Path Analysis: <br /> The following Codes/Standards have been evaluated during the review of the Closed-Loop Extractor <br /> and the Processing area/methods indicated. <br /> 314-55-104 WAC —> NFPA 30,2015 <br /> NFPA 54,2015 Sections:4.1;4.2; <br /> NFPA 58, 2014 > <br /> 5.2;5.7;5.9; 6.7; <br /> NFPA 497,2012 > Sections: 5.2;5.3 6.18;6.20; 7.3 <br /> NFPA 70 > Article 500(b)(2) <br /> ASME BPVC VIII Division 1—> Sections: UG; UW; UHA <br /> IBC 2012 > Sections: 306;307;414;415;508;Ch.7;Ch.9;Ch. 10; <br /> IMC 2012 —> Ch.34 <br /> IFC 2012 --> <br /> Chapter 4,Chapter 5 <br /> —> Chapter 7,Chapter 50,Chapter 61 <br /> NFPA 58-2014 <br /> 4.1.1 Systems or Components assembled to make up systems shall be approved. Cylinders less than 120 <br /> gallons. Container Valves, connection manifold valve assemblies, regulators, and pressure relief valves. <br /> 4.2.2 Odorization is not required as the R600/a is delivered from the manufacturer or distributor. The <br /> addition of Odorization damages the processed materials and shall increase the risk of the process by <br /> requiring persons untrained in odorization to perform this task. Odorization is not required and is not to <br /> be performed by processors for the purpose of oil extraction by a Professional Grade Closed Loop <br /> Extractor. A gas monitoring system is used to detect and monitor levels of the LP-Gas used. <br /> 5.2.3.1 DOT and ASME Designed containers are used for the storage of Solvents. No other containers <br /> are used for this process. The Extraction equipment is designed to the rules of ASME BPVC VIII Division <br /> 1, and the Butane tank(container) is a DOT approved container with a 20 lb quantity of Butane (R600/a) <br /> 5.2.4.2 The Maximum Allowable Working Pressure (MAWP) has been calculated to the current ASME <br /> Boiler and Pressure Vessel Code VIII Division 1. The MAWP has been identified and listed within this <br /> report. The process pressure never exceeds the MAWP. <br /> 5.2.8.1 (A)The Solvent vessel is marked according to the section, "Flammable" and "Butane" <br /> 5.2.8.4 Warning Labels that contain unodorized LP-Gas products shall be marked "NOT ODORIZED", <br /> Letter height 3/8", Border Width 1/16". The equipment and the room have the appropriate warning <br /> labels affixed. <br /> 5.7.1 Materials. All processing equipment such as the recovery pump,valves, fittings, seals and <br /> extracting piping meet the compatibility requirements for this process and solvent. <br /> 9/1/2015 Project: 150703 Terpp MK IV CLE Report Page 41 of 44 <br /> KD Doc. 150703ER <br />