Accessibility <br /> Both toilet rooms in the first floor offices should be shown on the drawings as <br /> accessible, per ICC A117.1-2009 section 603. <br /> a. The five foot clearance from the wall parallel to the water closet and the sink <br /> should be dimensioned on the drawings, per ICC A117.1-2009 figure 604.3. <br /> b. Stairs should be removed from the entry to the toilet room, to provide a level <br /> access from the offices, per ICC A117.1-2009 section 302. Alternatively, a ramp <br /> can be provided. <br /> c. A clear floor space per ICC A117.1-2009 section 305.3 should be shown on the <br /> drawings per ICC A117.1-2009 section 603.2.2, exception 2. <br /> d. Elevations should be shown on the drawings for both toilet rooms, to meet the <br /> requirements for grab bars, clearances, fixture heights and fixture locations. <br /> e. If a shower is provided, it should be shown on the drawings to be accessible, per <br /> ICC A117.1-2009 section 608. <br /> ✓ 2. New lavatories should be shown on the drawings in section to be no higher than 34 <br /> inches, measured to the higher rim or counter surface, per ICC A117.1-2009 section <br /> 606.3. <br /> a. Where exposed, piping for hot water should be shown on the drawings to be <br /> protected, per ICC A117.1-2009 section 606.6. <br /> e73. Door glazing should be shown on the drawings to meet the vision light requirements of <br /> ICC A117.1-2009 section 404.2.10. <br /> Energy <br /> ✓1. New exterior walls, windows and doors should be shown on the drawings to comply with <br /> WSEC Table R402.1.1 for energy requirements. <br /> Mechanical <br /> 1. New exhaust fans with the minimum required cfm should be shown on the drawings for <br /> new kitchenettes, and new toilets, per IMC table 403.3 and section 403.8.6, as amended <br /> by State of Washington. <br /> a. The new residential toilet exhaust on the second floor should be designed as a <br /> whole house fan. <br /> b. Both lower floor commercial toilets and kitchenettes are considered new, since <br /> they were modified without approvals from the`-1994 permit plans. <br /> 2. New mechanical for outside air will be required for the new interior office, per IMC table <br /> 403.3, as amended by State of Washington. <br /> All codes cited refer to the 2012 International Building Code (IBC), the 2012 International Fire <br /> Code (IFC), the 2012 International Mechanical Code (IMC), the 2012 International Property <br /> Maintenance Code (IPMC) and the 2012 Washington State Energy Code (WSEC), as amended <br /> by the State of Washington and adopted by the City of Everett. The current IBC referenced <br /> Page 4 <br />