Laserfiche WebLink
5. Provide minimum 100 CFM fan vented to the exterior in the kitchen. <br /> 6. Label all rooms for its intended use i.e., Bedroom, kitchen, living room, dining room, <br /> bathroom. <br /> 7. Drawings should be drawn to standard architectural format, including double lines for all <br /> partitions. <br /> 8. Provide smoke alarms per section R314, smoke alarms shall be 110 volt with battery <br /> back—up and interconnected. <br /> 9. Projections in the 5'-0"side yard setback shall be protected on the underside with one- <br /> hour fire- resistive construction, with no openings allowed. <br /> 10. Show how attic is ventilated. <br /> Please prepare a response letter showing where each item in this correction letter is <br /> addressed on the plan set. <br /> Upon resubmittal of the drawings, your application will be given priority and plan review will <br /> recommence. <br /> All required submittals shall be of sufficient detail and contain sufficient information to ensure <br /> that the proposed structure will be constructed in compliance with all adopted codes. <br /> Sincere), <br /> „AL,/ /fri <br /> Jeff Heilman <br /> Development Technician <br /> 425-257-8976 <br /> Email: jheilman a©ci.everett.wa.us <br /> / i <br /> S:\1Common\Clerical\]Heilman\!Hellman permit response.doc <br /> f�.. <br />