Laserfiche WebLink
7. Specify all components for all roofs, walls and floors. Specify moisture barriers, roof <br /> sheathing. Wall sheathing is called out as 3/8" plywood in one detail and 1/2" plywood <br /> on elevation. Please clarify. <br /> 8. Provide gravity calculations for the roof structure and the floor joists (2x4, 4x4, and <br /> 4x10). <br /> 9. Drawings are not drawn to scale. The building appears to be taller than the dimensions <br /> shown. Please clarify. <br /> Please prepare a response letter showing where each item in this correction letter is <br /> addressed on the plan set. <br /> Upon resubmittal of the drawings, your application will be given priority and plan review will <br /> recommence. <br /> All required submittals shall be of sufficient detail and contain sufficient information to ensure <br /> that the proposed structure will be constructed in compliance with all adopted codes. <br /> Sincerely, <br /> Jeff Heilman <br /> Development Technician <br /> 425-257-8976 <br /> Email: jheilman@ ici.everett.wa.us <br /> /9C•\1('nmmnn\flarira l\1Hailman\RW17(17-MR(11 11,th St SF1 rinr <br />