All Weather Insulated Panels <br /> oad <br /> A IP ALL WEATHER Vacaville, <br /> ie, A 5688 <br /> Vacaville,CA 956$8 <br /> INSULATED PANELS PH:(707)359-2280 <br /> FAX:(707)359-2287 <br /> 03/07/17 <br /> Fixture Mounting Design Guidelines <br /> Insulated metal panel facings may be used to support accessories and ancillary fixtures such as lighting, <br /> electrical equipment,pipes,conduit,signage,etc. <br /> The fastening procedures and design criteria for mounting onto the panel facings are outlined below: <br /> General <br /> 1. Nominal screw sizes shall be minimum#12 diameter(.210") <br /> 2. Self-drilling fasteners must penetrate beyond the panel facing a minimum of 3 pitches of thread <br /> 3. Fasteners may be spaced no closer than 12"on center along any direction. <br /> 4. Allowable design loads provided in the table on the following page are applicable to 26 gauge, <br /> 24 gauge and 22 gauge facings. <br /> Ceilings <br /> 1. Fastener spacing shall be designed based on the allowable fastener pullout values given in the <br /> table on the following page. <br /> 2. If the design load exceeds the allowable load, fasteners shall be fastened through entire <br /> thickness of panel into a backer support to resist equipment dead load. <br /> 3. Larger collateral loads including, but not limited to, HVAC, ductwork or sprinklers must be <br /> directly supported by the building framing and not by the ceiling panels. <br /> 4. The design load of the entire ceiling system will also need to be verified to ensure that any <br /> ceiling collateral loads are included. <br /> 929 Aldridge Road Vacaville,CA 95688 PH 707-359-2280 FX 707-359-2287 <br />