<br /> � � � February 12, 1991
<br /> 2 1991 •�:,, . :i�
<br /> .. .CITY OF EVEREi'T..'
<br /> � y � Publlc Works pe
<br /> r� .� pL
<br /> y RALPH QUAAS
<br /> ° y CITY FLORAL the Evergreen
<br /> � � r 2802 COLBY AVENUE ono�
<br /> � � EVERETT W!1 98201 everett
<br /> �� .�r.: .
<br /> 78110AKE5 � 25B�PiB1 � �, 1 "��
<br /> RE: FIRE PREVENTION INSPECTION , eveaEn.wssMu+cron . '.��_
<br /> ' eezo� r .� '
<br /> A partial inspection was made oP your business located at 2802 Colby FIREDEFANTMENi
<br /> Rvenue. 7he i�spection was limited to emergency exiting and fire
<br /> access problems in the basement with the intent of beginni�g a process
<br /> resulting in a resolution of life safety and firefighting problems
<br /> inherent in this building.
<br /> The following code provisions apply to these problems:
<br /> . i• ' •: :
<br /> 1. The 1988 Uniform Fire Code, Article 1, Section 1.103(b) states "The :�4 �' -:, ', � ,
<br /> � provisions of this code shall apply to e�.3.sting conditions as well as to :;;"r. "' ~
<br /> � ��( conditions arising after the adoption thereof, except that crnditions � ; .��,I " 't
<br /> legaily in existence at the adoption oP this code and not in strict , �" �.I" ,'• I
<br /> y. •i �
<br /> i • compliance therewlth shall be permitted to continue only if, in the p. F, �
<br /> I �� opinion of the chief, they do not constitute a distinct hazard to life or .''"�„��i��:l �
<br /> +� propertY•" ,I ' :, . i :- :�i
<br /> � 2. The 1988 Uniform Fire Code, Article 10, Section 10.306(b), and the �';i. {
<br /> Uniform Building Code, Chapter 38, Section 3802, state ". . an automatic �,`. �, �, �
<br /> sprinkler syste�n shall be installed: 1. In every story or hasement of all � �-s
<br /> �I �'� buildings when the floor area exceeds 1500 square feet and there is not ��•� � �-'' �'
<br /> provided at least 20 square feet of opening entirely above the ad,joining �,
<br /> ground level in each 50 lineal feet or fraction thereof of exterior wall '.::a ' �1
<br /> '�'"' i� the story or basement on at least one side of the building. Openings :s;`�; i:, :,�"
<br /> � shall have a minimum dimension of not less than 3D inches. Such openings _- -f'
<br /> shall be accessible to the fire department from the exterior and shall
<br /> not be obstructed in a manner that fire fighting or rescue cannot be �
<br /> + " � . .
<br /> accomplished from the exterior. When openings in a story are provided on N; i;�l
<br /> �� ' only one side and the opposite wall of such story Ss more than 75 feet "�d�,� �' ;:
<br /> from such openings, the story shall be provided with an approved "� 'f
<br /> ' automatic sprinkler system, or openings as specified above shall he ' •��" ��
<br /> �) �► provided on at least two sides of an exterior wall of the story. If any � ! �•�`�;,, �"
<br /> ��r� portion of a basement is located more thsn 75 feet from openings required ; y, :
<br /> in this section, the basement shall be provided with an approved , '�M1,� :, ' i
<br /> automatic sprinkler system." ' =��' + ''