Laserfiche WebLink
1 <br /> rt <br /> 19. All fire alarm control panels(FACP)and sprinkler valves shall be in heated rooms or closets with <br /> standard man door access. Locations shall be approved by the Fire Code Official(NFPA 13 <br /> 8.16.4.1.3). <br /> 20. The location of Fire Department connections(FDC)and post indicator valves(PIV)shall be <br /> determined by the Fire Code Official. If immediate outside man door access is available to the <br /> sprinkler valves (risers),a PIV will not be required. <br /> 21. Where elevators are provided in buildings, at least one elevator shall be provided for fire <br /> department emergency access to all floors. The elevator car shall be of such a size and arrangement <br /> to accommodate a 24-inch by 84-inch ambulance stretcher in the horizontal,open position and shall <br /> be identified by the international symbol for emergency medical services(star of life). The symbol <br /> shall not be less than 3 inches high and shall be placed inside on both sides of the hoistway door <br /> frame. <br /> Exception: If all stories within the building have direct, accessible egress to grade(EMC 16.01, <br /> Section L). <br /> 22. Fire apparatus roads shall have a minimum unobstructed width of 26 feet in the immediate vicinity <br /> of any building or portion of building more than 30 feet in height.At least one of the required access <br /> routes shall be located within a minimum of 15 feet and a maximum of 30 feet from the building <br /> and shall be positioned parallel to one entire side of the building. See 2012 IFC,Appendix D, D105.3. <br /> Note: If ladder access cannot reach the roof,a roof access hatch must be provided. Everett Fire <br /> Department ladder maximum reach is 90 feet at 75% ngle setup. <br /> Allan Oi -n, Planning Director <br /> City of Everett Responsible Official <br /> There is no appeal period for this addendum. <br />