d. Please document the accessible route to the primary entrance door, per ICC-A117.1-2009 <br /> section 403.4 to include conforming curb cuts, if used, and accessible door hardware on the <br /> drawings. <br /> e. The width of the exterior accessible route should be shown to be 44 inches, per IBC section <br /> 1102.1, as amended by the State of Washington. <br /> f. Accessible parking signage should indicate compliance with height and content of signage per <br /> ICC/ANSI A117.1-2009 section 502.7. <br /> Energy <br /> 1. Please include actual code section language on the drawings for interior and exterior lighting <br /> controls, sensors, and all other methods of compliance covered in electrical power and lighting <br /> systems per WSEC section C405. <br /> All codes cited refer to the 2015 International Building Code (IBC), the 2015 International Existing <br /> Building Code (IEBC), the 2015 International Property Maintenance Code (IPMC), the 2015 International <br /> Fire Code (IFC), the 2015 International Mechanical Code (IMC), and the 2015 Washington State Energy <br /> Code (WSEC), as amended by the State of Washington and adopted by the City of Everett. The current <br /> IBC referenced standard for accessible design is the 2009 "Accessible and Usable Buildings and Facilities" <br /> (ICC/ANSI A117.1). Federal ADA regulations and standards may be more restrictive. Compliance with <br /> these regulations is the responsibility of the tenant and owner of the building. Upon resubmittal of the <br /> drawings, your application will be given priority and plan review will recommence. <br /> M� <br /> Meg Haley, RA • Building Plans Examiner-Plan Review Architect • Everett Public Works,3200 Cedar St., Everett,WA 98201 • <br /> 425-257-8813 • mhaley@everettwa.gov• everettwa.�ov/permits <br /> CITY OF EVERETT PERMIT SERVICES 3200 CEDAR ST, EVERETT, WA 98201 425-257-8810 <br /> website: www.everettwa.qov/permit general email: everetteps(a�.everettwa.qov <br /> °"` J � <br />