Laserfiche WebLink
WIRING <br /> NOTE: All wiring must conform to applicable local codes, ordinances, and <br /> regulations.This module is intended for power limited wiring oniy. <br /> 1. Install module wiring in accordance with the job drawings and appropri- <br /> ate wiring diagrams. <br /> 2. Set the address on the modute per job dra�vings. <br /> NOTE: Some panels support extended addressing. In order to set the <br /> module above address 99 on compatible systems,carefully remove the <br /> stop on the upper tntary switch with thumb in the direction shown in <br /> Figure L <br /> NO'1'E:Monitor module L(using terminals 6 and 7)responds at the ad- <br /> dress set on the code switches.Monitor module H(using terminals 8 and <br /> 9)will automatically respond at the next higher address.For example,if <br /> the code switches are set to 7G,module L will respond at address 7G and <br /> module H will respond at address 77.Use caution to avoid duplicate ad- <br /> dressing of modules on the system. <br /> 3. Secure module to electrical box (supplied by installer), as shown in <br /> Figure 2A. <br /> FIGURE 3.TYPICAL 2-WIRE INITIATING CIRCUIT CONFlGURATION,NFPA STYLE B: <br /> TO NEXT �—� �,.,,��-��FROM PANEL OR <br /> DEVICE �+� ���T��pREVIOUS DEVICE <br /> TWO INITIATING DEVICE CIRCUITS(L&H),EACH <br /> POWER LIMITED TO 240 NA� 11.7 VDC MAX. MONITOR <br /> MODULE <br /> 47k EOL (� CONNECT MODULES TO LISTED <br /> RESISTOR H � � o � U COMPATtBLE CONTROL PANELS ONLY <br /> ELR-47k � <br /> 9 `se>esa � �—� <br /> . B��3 2 �+� � <br /> 47k EOL 6�� 3 SIGNAL LINE CIRCUIT{SLC� <br /> RESISTOR L s a a 32 VDC MAX.SHIELDED-TWISTED <br /> ELR-47k `" o"°°"`� PAIR IS RECOMMENDED <br /> � O O � ALL WIRING SHOWN IS <br /> UL LISTED CONTACT CLOSURE DEVICES MAY SUPERVISED AND POWER UMITED <br /> BE USED.DO NOT MIX FIRE ALARM INITIATING, <br /> SUPERVISORY,OR SECURITY DEVICES ON THE MONITOR A TERMINALS 6&7 <br /> SAME INITIATING DEVICE CIRCUIT. � )RESPONDSATADDRESS <br /> SET ON CODE SWITCHES.MONITOR B(TERMINALS 6&9) <br /> INSTALL CONTACT CLOSURE DEVICES PER RESPONDS AT NEXT HIGHER ADDRESS. <br /> MANUFACTURER'S INSTALLATION INSTRUCTIONS. <br /> C0608-02 <br /> 9000-0592 2 I56-2750-002 <br /> m2007 Gamewell-FC[ <br />