Laserfiche WebLink
} i + <br /> 5. The existing toilet room and door hardware should be modified to the extent feasible for <br /> adding dine-in customers where the total occupant load in the space is less than 30: <br /> a. Door hardware should be shown to be accessible on the door schedule, for both <br /> new and existing doors, per IEBC section 410.7 for adding dine-in customers. <br /> b. Please show the required clear floor space per ICC-A117.1-2009 section 305.3 <br /> beyond the arc of the door in the existing toilet room.. <br /> c. Please indicate if there is 5'turning space when the door is closed, per ICC- <br /> A117.1-2009 section 603.2.2, exception 2, in the existing toilet. <br /> d. The toilet paper dispensers in the existing toilet room should be shown on the <br /> toilet room elevations to meet the requirements of ICC-A117.1-2009 section <br /> 604.7, per IEBC section 410.7 for adding dine-in customers. <br /> Energy <br /> 1. Please identify the number of light fixtures and ceiling tiles to be replaced on a reflected <br /> ceiling plan. If the number of light fixtures to be replaced is over 50%, please include a <br /> calculated lighting summary from the forms available on NEEC.NET to verify compliance <br /> for the interior lighting power allowances per WSEC table C405.2 (1). <br /> Deferred permits <br /> 1. Mechanical: Fan and mechanical ducting for exhaust fan from new and existing public <br /> toilet rooms and providing ventilation and exhaust to dining rooms, per IMC table <br /> 403.3.1.1, some of which is amended by WA State. <br /> 2. Sign: Canopy support repair, new awning, and signage. <br /> All codes cited refer to the 2015 International Building Code (IBC), the 2015 International <br /> Existing Building Code (IEBC), the 2015 International Property Maintenance Code (IPMC), the <br /> 2015 International Fire Code (IFC), the 2015 International Mechanical Code (IMC), and the <br /> 2015 Washington State Energy Code (WSEC), as amended by the State of Washington and <br /> adopted by the City of Everett. The current IBC referenced standard for accessible design is <br /> the 2009 "Accessible and Usable Buildings and Facilities" (ICC/ANSI A117.1). Federal ADA <br /> regulations and standards may be more restrictive. Compliance with these regulations is the <br /> responsibility of the owner of the building. <br /> Upon submittal of the drawings, your application will be given priority and plan review will <br /> recommence. If you have any questions, please call me at 425-257-8813. <br /> Sincerely, <br /> M� <br /> Meg Haley, RA <br /> P�rn��ii Services, City of Everett, WA <br /> Di��ct: 425-257-831;s <br /> CITY OF EVERETT PERMIT SERVICES 3200 CEDAR ST, EVERETT, W,4 98201 425-257-8810 <br /> website: www.everettwa.qov/permit January 24, 2017 email.� everetteps(a�everettwa.pov <br /> ; " <br /> _ .F <br />