IE <br /> 5' <br /> b. Grease duct leakage test coordinated with the schedule of the city inspector <br /> on-site such that the installation can be reviewed with the light test prior to <br /> use or concealment, per IMC 506.3.2.5. <br /> c. Grease duct support materials and attachments, per IMC section 506.3.3. <br /> 8. 40 inch minimum termination of discharge exhaust opening should be dimensioned <br /> on the drawing section, per IMC section 506.3.12.1. <br /> 9. A light test affidavit should be provided to inspector on-site at a time where the <br /> inspector can review the Type I hood and duct installation, per IMC section <br /> 506.3.3.1. <br /> Upon resubmittal of the drawings, your application will be given priority and plan review will <br /> recommence. Applicable codes include the 2015 International Building Code, the 2015 International <br /> Existing Building Code, the 2015 International Fire Code, the 2015 International Mechanical Code, and <br /> the 2015 Washington State Energy Code (WSEC) as amended by the State of Washington and adopted <br /> by the City of Everett. Revisions or additions may be required by other departments (such as Utilities, <br /> Planning, or Fire). <br /> Sincerely, <br /> Mei <br /> Meg Haley, RA <br /> Plan Review Architect <br /> Permit Services, City of Everett, WA <br /> Direct: 425-257-8813 <br /> Front Counter: 425-257-8810 (Option 8) <br /> Permits everettwa.gov/permits Building Codes everettwa.gov/codes Addressing Questions everettwa.gov/maptools <br /> CITY OF EVERETT PERMIT SERVICES 3200 CEDAR ST, EVERETT, WA 98201 425-257-8810 <br /> website:www.everettwa.gov/permit general email:everettenseeverettwa.pov <br /> �w�, f <br /> �F�n' <br />