Laserfiche WebLink
8. The location of Fire Department connections(FDC)and post indicator valves(PIV) <br /> shall be determined by the Fire Code Oficial. If immediate outside man door access <br /> is available to the sprinkler valves(risers),a PIV will not be required.RemoteFDC. <br /> 9. Premise Identification Premises shall be clearly identified by the correct address at <br /> the street entry. Buildings shall be clearly identified so as to be visible and legible <br /> from the access road. Individual apartments and suites,where applicable, shall be <br /> clearly and legibly identified from the access road. EMC 16.03, Section 505.1.1 <br /> (Address Posting Policy). <br /> 10.All fire alarm control panels(FACP) and sprinkler valves shall be in heated rooms or closets <br /> with standard man door access. Locations shall be approved by the Fire Code Official <br /> (NFPA 13,2013 edition, section 8.16.4.1.3). <br /> 11.The location of Fire Department connections(FDC)and post indicator valves(PIV) shall be <br /> determined by the Fire Code Official. If immediate outside man door access is available to <br /> the sprinkler valves(risers),a PIV will not be required. <br /> { <br /> Planning Director Decision Page 7 of 7 <br /> HC 16-001 <br />