Laserfiche WebLink
1 <br /> The absence of monitoring for the alarm system will be cause for postponing Fire <br /> Department inspection and testing and shall result in denial of occupancy. <br /> A copy of NFPA 72 Record of Completion form must be filled out prior to final occupancy <br /> (NFPA 72,2013 Edition,Chapter 7,pages 107-147). 2015 IFC,907.7.2 <br /> Call for design requirements per Authority Having Jurisdiction. <br /> Automatic smoke detection is required. <br /> FA Panel can share both buildings.Annunciator required in'lobby. <br /> 5. Fire Suppression(Sprinkler) System-An approved automatic suppression system shall be <br /> provided as required by City Ordinance No. 3021-07,EMC, Chapter 16.76. <br /> Plans for any such system shall be submitted to the Engineering&Public Services <br /> Department for examination and approval. Such plans shall include plans for the <br /> underground mains that will supply the sprinkler system. <br /> The type of sprinkler to be installed will be an NFPA 13R. Sprinkler installation shall not <br /> begin without an approved and stamped set of plans from the Engineering&Public <br /> Services Department. The Fire Department will also review the plans and shall field <br /> inspect the installation based only on approved plans that must be on site. Changes to plans <br /> must be approved by both the Engineering&Public Services and Fire Departments. <br /> Aboveground sprinkler piping shall be hydrostatically tested as established in NFPA <br /> Standard 13. Underground piping shall be hydrostatically tested and flushed as established in <br /> NFPA Standard 24 for private fire mains. (Below-ground piping must be installed by <br /> Washington State Licensed Underground Sprinkler line certified "U" installers. For <br /> further information,contact the State Fire Marshal's Office at(360)596-3900 or <br /> contact the Everett Fire Department at(425)257-8104.) All such tests shall be witnessed <br /> by a Fire Department inspector. Call (425)257-8104 or(425)257-8120 to make an <br /> appointment for inspection. <br /> Contractors'materials and test certificates shall be submitted to the Everett Fire Department <br /> prior to issuance of any Certificates of Occupancy. 2015 IFC,WA State Amendment <br /> 903.3.5.3,Page 111. <br /> Call(425)257-8104 for more information.Remote FDC if possible. <br /> 6. Sprinkler shutoff valves shall be provided on each floor in every building three or <br /> more stories high,including below-grade floors. <br /> 7. A floor map shall be included at each stair landing(11"x 17"size)and at each <br /> elevator landing(16"x 20"size)showing the layout and room numbering of the <br /> floor. <br /> Planning Director Decision ' Page 6 of 7 <br /> I-tC 16-001 <br />