Laserfiche WebLink
A <br /> 5. Show plan view of all levels in existing dwelling. Label all spaces. Show smoke alarms/ <br /> R314 IRC and carbon monoxide alarms per R315 IRC. <br /> 6. Vaulted ceilings are required to be insulated to minimum R-38 per table R402.1.1 <br /> footnote k. (see state amendment to WSEC Was> Title 54> Chapter 51-11R-40211). <br /> Size framing member for the required insulation depth with minimum 1"clear air space. <br /> 7. From permit C0510-009, "no sleeping rooms approved in basement" label bedrooms as <br /> proposed. Verify Egress and smoke alarms (110 Volt with battery back-up <br /> interconnected). <br /> 8. No gable vent allowed where projection (overhang) extends into the 5'0"side yard <br /> setback. Dimension projection on gable side of roof on elevation drawing and/or section. <br /> Please prepare a response letter showing where each item in this correction letter is <br /> addressed on the plan set. <br /> Upon resubmittal of the drawings, your application will be given priority and plan review will <br /> recommence. <br /> All required submittals shall be of sufficient detail and contain sufficient information to ensure <br /> that the proposed structure will be constructed in compliance with all adopted codes. <br /> Sincerely,7-("/V-4, <br /> Je <br /> Development Technician <br /> 425-257-8976 <br /> Email: iheilman@ci.everett.wa.us <br /> ii ,.., ) <br /> x <br /> S:\1Common\Clerical\]Heilman\BW1310-003(5013 S 3rd Ave).doc <br /> y <br /> " <br />