Laserfiche WebLink
8. Footnote e to Table 2902.1 would allow a reduction in toilets serving the Group E <br /> occupancy. <br /> 9. Each of the two restrooms with more than 6 toilets/urinals requires an ambulatory toilet <br /> stall. Section 1109.2.2 <br /> 10.A cut-sheet should bep rovided that shows that the group hand-wash station is <br /> accessible. Section 1109.2.3 <br /> Energy <br /> 1. The above and below grade walls should be shown with R-21 Insulation.Table C402.1.3 <br /> 2. The roof should be shown with R-38 insulation. Table C402.1.3 <br /> 3. The requirement for reduced air infiltration should be noted on the plans. Section <br /> C406.9 <br /> 4. Intermediate framing requires R-10 insulation in the window headers. Table C402.1.3 <br /> All codes cited refer to the 2015 International Building Code (IBC), the 2015 International Fire <br /> Code (IFC), the 2015 International Mechanical Code (IMC), and the 2015 Washington State <br /> Energy Code (WSEC), as amended by the State of Washington and adopted by the City of <br /> Everett. The current IBC referenced standard for accessible design is the 2009 "Accessible and <br /> Usable Buildings and Facilities" (ICC/ANSI A117.1). Federal ADA regulations and standards may <br /> be more restrictive. These comments address building issues only. Additional revisions or <br /> additions may be required by other departments (such as Utilities,Traffic, Planning or Fire). All <br /> required submittals must be of sufficient detail and information to ensure that the proposed <br /> structure will be constructed in compliance with all adopted codes. <br /> Sincerely, <br /> Ton ee <br /> Building Official <br /> CITY OF EVERETT • 3200 Cedar Street • Everett,WA 98201 ,•,(.925)257-8813 • Page 2' <br />